background image

iRIS8 - Addressable Fire Alarm Panel 

– Installer Programming  

 

 

Icon 

Description Status Icons 

 

Loading data; Resetting. The icon is flashing while the process is running on. 

 

Saving configuration. The icon is active during running of saving data process.  

 

Day time operation mode. The process signals from detectors are with enhanced sensitivity (set for 
every detector). 

 

Night time operation mode. The process signals from detectors are with enhanced sensitivity (set for 
every detector). 

 

Addressing Mode is running on. The panel is in operating mode for setting or changing device addresses, self- 
or auto-addressing procedure; the panel does not follow the status of the devices and is idle for other kind of 
operations till the end of the addressing procedure. 

 

Evacuation time for leaving the premises is running on. The icon is flashing together with the other active icons 
and back counting time for leaving the premises before panel outputs* activation.  
 

 

 

 

Set Delay for panel outputs* activation. The icon is flashing, changing with the icon for evacuation. 
 

 

 

 

 
The icons for current status of the panel have the following meaning: 

Type 

Icon 

Mode 

Description 

Sounders 

(loop devices, panel outputs*) 

 

Standby 

Not activated Sounder outputs. 

 

Fault 

Not activated Sounder outputs; fault detected. 

 

Fire alarm 

Activated Sounder outputs. 

 

Fire alarm 

Activated Sounder outputs in fault. 

 

Disabled** 

Sounder outputs are disabled. 

Fire Brigade Output 

(panel*) 

 

Standby 

Standby mode, not activated Fire Brigade output. 

 

Fault 

Not activated Fire Brigade output; fault detected. 

 

Fire alarm 

Activated Fire Brigade output. 

 

Fire alarm 

Activated Fire Brigade output in fault. 

 

Disabled** 

The Fire Brigade output is disabled. 

Fire Protection 

(Extinguishing) Output 

(panel*) 

 

Standby 

Not activated Fire Protection output. 

 

Fault 

Not activated Fire Protection output; fault detected. 

 

Fire alarm 

Activated Fire Protection output. 

 

Fire alarm 

Activated Fire Protection output in fault. 

 

Disabled** 

The Fire Protection output is disabled. 

 
* Outputs type Sounder, Fire Brigade and Fire Protection (Extinguishing) of the iRIS8 fire alarm panel or other fire panel in the network from which the 
fire event is received.  

** 

Attention: The iRIS8 indication shows that there are one or more fire panels in the network with disabled for operation output. You can check the 

DISABLE events menu to review the numbers of these panels.  

Содержание iRIS8

Страница 1: ...e and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read The information in this manual is a subject to change without notice iR...

Страница 2: ...ry Devices 17 3 2 2 Current Status of Periphery Device 17 3 2 3 Main Power Supply Unit Screen 18 3 2 4 Input Output Module Screen 19 3 2 5 Loop Controller Screen 19 3 2 6 Loop Devices General Informat...

Страница 3: ...ny Logo Setting Screen Saver 62 3 5 10 FAT FBF ESPA444 Settings Menus 63 3 6 Restore Defaults 65 3 7 Save the Configuration 65 4 MAINTENANCE SYSTEM MENUS 66 4 1 Setting Time 66 4 2 Setting Date 66 4 3...

Страница 4: ...s Performance of power supply Pass Response delay response time to fire Pass Operational reliability Pass Durability of operational reliability and response delay temperature resistance Pass Durabilit...

Страница 5: ...suse In the case of a reasonable number of unsuccessful attempts to repair the product covered by this guarantee the manufacturer s liability shall be limited to the replacement of the product as sole...

Страница 6: ...age and contamination of the sensitive TFT screen during operation Do not use sharp instruments for pressing the screen like screwdrivers tweezers or pliers because they can scratch or break the plast...

Страница 7: ...delay for one or several panel s outputs POWER green Presence of power supply main or back up or both DISABLE yellow Lights on permanently in active disablement in the system TEST yellow Lights on pe...

Страница 8: ...There is no indication for general fire or pre alarm event Performing of zone testing is described in details in item 4 7 1 Note The disabled for operation zones do not report for fire faults evacuati...

Страница 9: ...atus of the panel have the following meaning Type Icon Mode Description Sounders loop devices panel outputs Standby Not activated Sounder outputs Fault Not activated Sounder outputs fault detected Fir...

Страница 10: ...tenance menus and returning back to Main Screen 1 3 7 Sound Signalization The iRIS8 fire alarm panel is equipped with internal buzzer for sound signalization in case of events Signalization Descriptio...

Страница 11: ...or Text Introducing The text introducing is via virtual keyboard presenting access to different type of letters symbols and numbers The virtual keyboard is shown on the screen after pressing an active...

Страница 12: ...introducing is via virtual keyboard After pressing an active button for introducing digits in a menu the screen displays the virtual digit keyboard Enter confirmation button Backspace delete button U...

Страница 13: ...g the digit button in the middle Name Active field for setting additional description name for the selected zone number up to 40 digits Refer to item 2 3 for details about text introducing Zone Group...

Страница 14: ...vent to the respective zone 2 DEVICES Any detector activation within the system generates a PRE ALARM event to the respective zone but also awaits the activation of another detector from the same zone...

Страница 15: ...e alarm condition will be activated not only the sounders in the respective zone but also and the sounders in the associated to it Sounder Groups A B C The installer can organize up to 127 separate So...

Страница 16: ...umbers are displayed at the same time First are displayed the zone numbers from 1 to 60 The Enabled zone numbers are presented with active button in blue The Disabled zone numbers are presented with a...

Страница 17: ...f iRIS8 panel models and table represent the fixed factory addresses of the periphery devices which must be assumed during the initial power up and programming of the whole system Model iRIS8 System N...

Страница 18: ...button from the menu Note The message for Fault condition of a periphery device is displayed with a time delay up to 60 70 sec TYPE ERROR A device different from that saved has been detected at the r...

Страница 19: ...n Software version of the input output module At ADDRESS 12 is presented information about the output module OUT2 connected to second main power supply The OUT2 output module has the following hardwar...

Страница 20: ...ERROR For correct that you first need to remove wrong and then to save the new type of the device The loop controller TTE automatically recognizes the types of devices in the loop Every device is rec...

Страница 21: ...ess FIX TYPE button to correct or REMOVE button to dele No device found at the selected address the address is free To change the device operation status 3 press the active button next to system name...

Страница 22: ...Review Next to LOOP menu is situated button GRID VIEW for quick reviewing the operation status of all loop devices The devices are reviewed at several screens as 50 address numbers are displayed at t...

Страница 23: ...chnical specifications mounting etc 3 2 8 1 Optical Smoke Detectors Available models SensoIRIS S130 optical smoke detector white available also in black SensoIRIS S130 IS optical smoke detector with b...

Страница 24: ...refer to the installation manuals of SensoIRIS B124 standard base and the SensoIRIS detectors series When a Device Group Number is set 1 100 the RI OUT option is available to change as every pressing...

Страница 25: ...or controlling a LED remote indicator RI see the details in item 3 2 8 1 Day Class Temperature Setting the day class temperature for operation Night Class Temperature Setting the night class temperatu...

Страница 26: ...part In addition for this device only the installer can enable or disable the heat part of the detector The state of the heat part can be changed with pressing the button The class temperature of Sen...

Страница 27: ...vent generated with activation of the manual call point EVACUATE Immediate evacuation of the protected sites The sounders will be activated immediately as the set time delays 1 and 2 are ignored ALARM...

Страница 28: ...sound level between HIGH LOW as this depends on the number of the connected sounders to the loop HIGH Set in those cases when the number of the connected sounders to the loop is up to 30 sounders WSOU...

Страница 29: ...reen the installer can review the general and set the additional parameter Mode Press to choose from a list the mode of operation of the sounder see the screen below Sound Level Every pressing of the...

Страница 30: ...for the device Press the APPLY button to save the settings For detailed description of the main screen of the device see item 3 2 6 Press MORE button to access some additional information or settings...

Страница 31: ...he addressable SensoIRIS input output modules have built in isolator module which must be connected during installation For detailed description of the main screen of the device see item 3 2 6 Press M...

Страница 32: ...o the panel when is activated EVACUATE The input operates as fire detector and generates evacuation event to the panel when is activated GAS ALARM The input operates as gas detector and generates gas...

Страница 33: ...of the module is ON The fault will be cleared with switching off the power supply of the module including the external power supply unit and switching it on again Power Supply fault Missing or low ex...

Страница 34: ...ne or more of its outputs are connected conventional sounders and the Sounders Mode operation is set for the channel 3 2 8 11 Zone Modules Available model SensoIRIS MCZ conventional zone module The ad...

Страница 35: ...ly failure the fault message Power Supply Fault will appear on the status field of the device To configure the LED outputs operation you have to go to menu OUTPUTS see item 3 4 The Output Pulse Type s...

Страница 36: ...S TTE loops Now the installer can start mounting detectors and modules one by one The panel will set the displayed address number to the mounted device and automatically proceeds with next free addres...

Страница 37: ...s menu ADDRESSING SET ADDRESS The device must be prepared for connection to the panel The system automatically shows the first address in the system If the address is assigned the panel will display t...

Страница 38: ...dure of devices to the system configuration The self addressing procedure is suitable when there is great number of new devices to be connected to the panel The new devices are prepared for connection...

Страница 39: ...d To start auto addressing by ID numbers in the selected loop number press the Start Autoaddressing ID button Confirm with YES button to start The blinking system icon shows that the process is runnin...

Страница 40: ...l Fault LED will light on the front panel To find the devices with 0 address the installer has to enter in the installer s menu ADDRESSING LOOP ZERO ADDRESS The Zero Address Test will be performed to...

Страница 41: ...hen the input will be activated from a network device panel repeater number Zone Group This option is selected when the input will be activated from a zone in fire alarm or fault included in a group D...

Страница 42: ...access the additional settings for the loop type input Note that all introduces changes must be confirmed with APPLY button in this main screen Set the GROUP Number from 1 250 according the system con...

Страница 43: ...FUNCTION selection ZONE FIRE The activation is in case of fire alarm event in the set zone number ZONE FAULT The activation is in case of fault event in the set zone number ZONE DISABLED The activati...

Страница 44: ...E WEEK for activation Press the CHANGE button The days of the week are listed in a separate screen Enable ON setting those days of the week when the input has to be activated Press EXIT two times to r...

Страница 45: ...or FUNCTION selection SILENCE BUZZER Activation in case of silencing the buzzer in the system SILENCE SOUNDER Activation in case of silencing the sounders in the system RESET Activation in case of res...

Страница 46: ...ion of the input are listed after pressing the active button for FUNCTION selection COMMON FIRE Activation in case of Fire Alarm event in the system COMMON PREALARM Activation in case of PreAlarm even...

Страница 47: ...be activated from a zone in fire alarm or fault included in a group Press MORE button to access the additional settings for the zone group type input Note that all introduced changes must be confirme...

Страница 48: ...the current settings INPUT NUMBERS A grid view with available input numbers in the system Up to 50 input numbers can be reviewed at the same time To review the rest the installer has to use the large...

Страница 49: ...description for the output up to 40 symbols For text entering see item 2 3 Behavior This setting is for behaviour of the output in case of activation Every pressing of the button changes the setting...

Страница 50: ...ntroduced changes must be confirmed with APPLY button Set the loop device address loop number and number of the output terminal The available output numbers are displayed enclosed in brackets Confirm...

Страница 51: ...are listed after pressing the active button for FUNCTION selection SILENCE BUZZER The output will perform a silencing the buzzer in the system SILENCE ALARM The output will perform a silencing sounder...

Страница 52: ...every output number The logical interactions of how inputs will control the output are set on a map as it is presented on a separate screen after pressing the Edit Outputs Map button from the Outputs...

Страница 53: ...Information item 3 5 9 FAT FBF ESPA444 Protocols item 3 5 10 3 5 1 Setting Access Codes and Levels for Operation There are three access levels for control in iRIS8 addressable fire alarm panel with d...

Страница 54: ...eturns to ACCESS CODE menu showing the new code set into the Access Code active digit button Press APPLY button to save the change To change the Access Level press the active digit button next to ACCE...

Страница 55: ...k Every pressing of the button changes the status Enabled Disabled When the status is Disabled the panel is disconnected from the network and is not visible for the rest of the panels A fault message...

Страница 56: ...ation Press ADD button to confirm PRESENT The panel is in normal operation mode FAULT Fault mode problem with connection in the network THIS This is the current panel from which the other panels are r...

Страница 57: ...the Receiving Sending commands and messages for events for the iRIS8 itself can be done only via the other connected panels in the network IMPORTANT NOTES In case of making software or hardware Restor...

Страница 58: ...settings at SOUNDERS MODE submenu Sounders Mode Set the sounders operation mode Every pressing of the active button changes the state Common Zonal COMMON All sounders will be activated with no sense...

Страница 59: ...BE LAMP SOUND and SOUND STROBE The operation is same described above for the alarm settings Alert EVAC Voice Cycle Using the arrow buttons the installer sets the cycle for sounding of the sounders in...

Страница 60: ...of the building the sounders are activated with alarm sound tone The Stage 1 evacuation delay time starts running after finishing the set delays T1 and T2 in the system If Stage 1 time is set to 0 th...

Страница 61: ...EVAC VOICE CYCLE to be set and different from 0 The current settings on the EVAC ZONES screen are for respectively set Zone Group The EVAC ZONE settings can be set different for the separate Zone Grou...

Страница 62: ...the type of the printer connected to Printer terminal on the interface board of iRIS8 configuration The iRIS8 fire alarm control panel can operate with the following types of thermal printers Cannon t...

Страница 63: ...s operation between iRIS8 and FAT FBF control panel The table represents set for operation CHANNELS inputs outputs of a loop device and or periphery device used for communication with FAT FBF panel Pr...

Страница 64: ...dialer and sending a Fire alarm signal to the Fire Brigade site Panel fault output Output 3 This is an output for activation of the dialer and sending a Panel fault signal to a maintenance team or ot...

Страница 65: ...and Panel settings to restore the operation of the panel in the network The memory log file will not reset or cleared as all records will be saved It is recommended before making a Restore Defaults of...

Страница 66: ...Software Revision Firmware update of the panel item 4 9 Display Calibration of the screen review colors set backlight of the screen item 4 10 View Insulator Active Review the activated isolator in the...

Страница 67: ...ned OFF The icon on status bar is moon ON The Day Time mode is constantly turned ON The icon on status bar is sun Time Schedule Programming of a schedule list for all week days for using day time mode...

Страница 68: ...ED indication DELAY on the front panel is lighting on Time Schedule Programming of a schedule list for all week days for using time delay The button is always active regardless it is selected or not P...

Страница 69: ...rom the newest to the oldest registered in the log file The field Total Alarms Counter shows the total number of the registered alarm events in the system Use the up and down arrow buttons to scroll t...

Страница 70: ...ication during zone testing see item 1 3 2 To start zone testing enter MAINTENANCE TEST ZONE TEST The zone numbers are displayed in grid view The zones are reviewed at several screens as 60 numbers ar...

Страница 71: ...uzzer is sounding The panel will automatically exit the indication test mode after 5 seconds The colors of the system status indication LEDs are presented in item 1 3 1 4 7 3 Device Test This is a ser...

Страница 72: ...access to loop devices programming menus See for details item 3 2 6 for device settings and 3 2 7 for devices grid view mode 4 8 3 Zone Devices Press the ZONE DEVICES button This is a special grid vi...

Страница 73: ...acturer s official web site http www teletek electronics com or ask your local distributer of the equipment It is recommended first to save the system configuration with ProsTE software as TDF Teletek...

Страница 74: ...screen Do not use sharp instruments for pressing the screen like screwdrivers tweezers or pliers because they can scratch or break the plastic surface of the screen and the iRIS8 panel to become not o...

Страница 75: ...submenu to check the number and type of the supported colors Press the screen anywhere to return to DISPLAY menu 4 10 3 Setting the Screen Backlight ATTENTION Power Safe Backlight must be disabled fo...

Страница 76: ...ontain sealed lead acid batteries 24V 18Ah to provide standby power in the event of mains failure This battery has a life expectancy of around 4 years It is recommended that this battery be annually t...

Страница 77: ...iRIS8 Addressable Fire Alarm Panel Installer Programming 77 APPENDIX General Menu Structure PROGRAMMING MENUS Installers Access Level 3...

Страница 78: ...iRIS8 Addressable Fire Alarm Panel Installer Programming 78 APPENDIX General Menu Structure Continue MAINTENANCE MENUS Installers Access Level 3...

Страница 79: ...oIRIS BSOU IS Base with sounder Yes built in SensoIRIS BSST Base with sounder and strobe No SensoIRIS BSST IS Base with sounder and strobe Yes built in SensoIRIS MIO 04 Module with 4 outputs Yes must...

Страница 80: ...iRIS8 Addressable Fire Alarm Panel Installer Programming 80 APPENDIX C Initial Start up of the System...

Страница 81: ...T2 will start running when are enabled in MAINTENANCE OUTPUT DELAY menu The time delays are set for activation when the DISABLED LED on the front panel is lighting on The presented operation algorith...

Страница 82: ...ithm Continue Note When the general time delay for activation T1 is disabled T1 0 then the individually set T2 time delays for the activated zone in fire alarm start running In case of activation of m...

Страница 83: ...___ x 16 5mA ____ x 5mA WSOU IS ____ x 16 5mA ____ x 5mA WSST ____ x 22mA ____ x 12mA WSST IS ____ x 22mA ____ x 12mA BSOU ____ x 10mA ____ x 3mA BSOU IS ____ x 10mA ____ x 3mA BSST ____ x 10mA ____ x...

Страница 84: ...1 5s OFF AS1670 Evacuation 10 550Hz 440Hz 0 5Hz 11 970Hz 0 5s ON 0 5s OFF x 3 1 5s OFF ISO 8201 12 2850Hz 0 5s ON 0 5s OFF x 3 1 5s OFF ISO 8201 13 1200Hz 500Hz 1Hz DIN 33 404 14 400Hz 15 550Hz 0 7s 1...

Страница 85: ...ut Fault Circuit broken at Extinguishing output Fault Output Short Short circuit detected at Fault output Fault Output Fault Circuit broken at Fault output Fault Power AUX Short circuit the mains powe...

Страница 86: ...gnal from detector PreAlarm Fire alarm signal from detector in 2DEVICES or DOUBLE operation mode for zone Test Alarm Fire alarm signal from tested detector Loop Device Type Error A different than the...

Страница 87: ...English RevA 10 2021 www teletek electronics com Address Bulgaria 1407 Sofia 14 Srebarna Str Tel 359 2 9694 800 Fax 359 2 962 52 13 e mail info teletek electronics bg...

Отзывы: