iRIS8 - Addressable Fire Alarm Panel
– Installer Programming
71
The successful test is confirmed with a text message on
the screen “TEST ALARM” at alarm events list and single
long sound from the panel’s buzzer.
The number of the tested zone is lighting on the front
panel.
Reset the activated device to normal operation mode.
Continue in the same way testing the other devices
attached to that zone.
Before stopping the running zone tests, first make
sure that all activated devices are reset to normal
operation mode.
Go back to SYSTEM
– MAINTENANCE – TEST – ZONE
TEST and press STOP button.
The indication on the front panel will be cleared
automatically, as well the alarm events list.
Use EXIT button to return back to TEST Menus.
After finishing with zone testing, it is recommended to reset the panel from the main screen
– press MENU and then
RESET button.
4.7.2. Indication Test
The indication test allows the user to review the correct operation of the LED indication on the front panel and the
sound signal of the internal buzzer.
To perform the indication test, enter MAINTENANCE
– TEST – INDICATION TEST. All LEDs on the front panel start
blinking and the internal buzzer is sounding. The panel will automatically exit the indication test mode after 5 seconds.
The colors of the system status indication LEDs are presented in item
4.7.3. Device Test
This is a service menu for verification of communication between the panel and the devices connected to loop. The user
can select the loop and address number of a device and check the number of
communication packets at “Yes/No” field.
The connection is reset with RESET button on the top.
4.7.4. Sounder Output Test
This is a menu for testing the operability of the monitored
sounder outputs on the control panel’s PCB.
Note: The Sounder Output Test will be applied to all SND outputs of the used iRIS8 fire alarm panel. The number of the
SND outputs depends on the model and configuration:
- Single panel iRIS8 S (up to 4 loops)
– 1 SND output.
- Common configuration of iRIS8 S + iRIS8 Ext (up to 8 loops)
– 2 SND outputs. Both panels are mounted
together in a modular structure and connected via interface cable.
- Single panel iRIS8 B (up to 8 loops)
– 2 SND outputs.
Enter MAINTENANCE
– TEST – SOUNDER OUTPUT TEST.
To start the test, press the ON button.
Use EXIT button to return back to TEST Menus.
The sounder outputs will be activated together with the
LED TEST on the control panel and the icon indication on
the screen. No messages for events are generated.
To stop the test, press OFF button.