4.4. Setting Outputs Delay
This is a menu for setting time delay for activation of the panel’s outputs on the main PCB. This provides the possibility
of checking the authenticity of the alarm before the sounders and extinguishing on the site to be turned on (an official
visits the site and inspects for fire).
Enter MAINTENANCE
– OUTPUT DELAY menu.
By default, the time delay for all panel’s outputs is turned
OFF. To change the operation mode, press the button with
respective setting.
The time delay (T2)
is set for every of the panel’s outputs
on the main PCB: Sounder (SND), Fire Brigade (Fire R)
and Fire Protection (Fire P). The duration of the time
delay is set for every zone number individually
The operation mode is Enabled, when the button is
selected and inactive (grey color with black text):
•
OFF
– The Time Delay is turned OFF. The output is
activated immediately.
•
ON
– The Time Delay is turned ON. The output is
activated after a preprogramed time delay. The LED
indication DELAY on the front panel is lighting on.
•
Time Schedule
– Programming of a schedule list for
all week days for using time delay. The button is
always active, regardless it is selected or not.
Press APPLY button to confirm the set configuration
.
In the example: the delay for activation of the sounders
will be turned ON via set time schedule.
The delay for
activation of Fire Brigade and Fire Protection outputs is
constantly turned ON.
The TIME SCHEDULE is set after pressing the button
next to Sounder Delay, Fire Brigade Delay or Fire
Protection Delay field. The time schedule table is
programmed for every of the delays.
The time schedule table presents the preprogrammed
hours for turning ON and turning OFF the delay for
activation. The times are set for every day of the week.
During TIME ON the DELAY LED on the front panel is
active.
To set a time for ON/OFF, press the button corresponding
of the day of the week.
Use the arrows, or directly set the time via digit button
and virtual keyboard. Confirm the set time with APPLY
button. The panel will return to Time Schedule settings
screen as the new time is directly set for the respective
day of the week.
Use EXIT button to return back to Maintenance Menus.