iRIS8 - Addressable Fire Alarm Panel
– Installer Programming
64
The inputs and outputs (terminals of loop or periphery devices) are set for operation with their specific address and
channel number. For realization can be used inputs of SensoIRIS MIO-22, MIO-22 M, MIO-40, MINP M modules, and
for outputs can be used the programmable relay outputs of the panel, and outputs of SensoIRIS MIO-22, MIO-22 M,
MIO-04, MOUT modules.
The programmable inputs and outputs in iRIS8 panel are listed at the left side of the menu and have the following
meaning:
Door switch input
(Input 1)
This is an input for receiving a signal that the door of the key safe is opened. A warning
message will be generated.
Dialer ack input
(Input 2)
This is an input for receiving a signal that the fire brigade confirms the Fire Alarm signal
(the Fire Brigade team has received the signal sent from the iRIS8 panel through
Output 2).
Dialer fault input
(Input 3)
This is an input for receiving a signal that there is a trouble with the operation of the
dialer. The signal generates a Fault message visible on the panel’s log with description
of the device address and channel number. It is recommended to type individual name
for that input so to be easy recognizable.
Door unlock output
(Output 1)
This is an output for sending a signal from iRIS8 panel for unlocking the adapter box of
the key safe.
Fire alarm output
(Output 2)
This is an output for activation of the dialer and sending a Fire alarm signal to the Fire
Brigade site.
Panel fault output
(Output 3)
This is an output for activation of the dialer and sending a Panel fault signal to a
maintenance team or other unit for special support.
Sabotage output
(Output 4)
This is an output for activation of the dialer and sending a Sabotage alarm signal for
unauthorized opening of the key safe adapter box to a maintenance team or other unit
special support.
Note: Refer to Installation manual of iRIS8 panels for details about the connection to FAT/FBF control panel and
represented above Inputs and Outputs numbers.
The set configuration is correct, when all of the sections are filled in and there are
no messages “N/A” on the screen.
That will ensure the correct operation between iRIS8 panel and FAT/FBF control panel.
Note:
At first entering into the FAT/FBF programming menu the values set are “0” for all inputs and outputs. At the end
of the rows are
displayed messages “N/A”. After setting an address of a periphery device ones it cannot be set back to
“0”.
Example of a FAT/FBF menu programming:
For the realization of the connection between iRIS8 panel
and FAT/FBF panel are used two MIO-22 modules and
three of the programmable outputs of iRIS8 panel.
The MIO-22 modules are connected and addressed to
the first loop controller with address 3.
The following table represents the details of the programming:
Periphery Device
Loop Device
Channel
Type
Address
Type
Address
Number
Input 1
Loop
3
MIO-22
1
1
Input 2
Loop
3
MIO-22
1
2
Input 3
Loop
3
MIO-22
2
1
Output 1
OUT
2
-
-
1
Output 2
OUT
2
-
-
2
Output 3
OUT
2
-
-
3
Output 4
Loop
3
MIO-22
1
3