Installation
Note:
Push the slider up into the retaining nibs on the rear bracket. Failure to push the
slider up and secure it will result in station damage during installation.
Connect the red lead on the station to the positive terminal of the desired point on the room controller
and connect the black lead to the negative terminal of the desired point on the room controller. If pos-
sible, connect the SF123 stations to points 2-4. These are the default connection points for SF123s in a
single or dual bed installation.
l
To use an SF123 as a
Code Blue
switch, connect it to
Point 2 (Blue and Blue/White)
on the
room controller.
l
To use an SF123 as a
Bath
switch, connect it to
Point 3 (Red and Red/White)
on the room con-
troller.
l
To use an SF123 as an
Emergency
switch, connect it to
Point 4 (Orange and Orange/White)
on
the room controller.
l
If a custom call type is desired, note which point the SF123 station is connected to using the
worksheet in the back of this manual. This information will be used during configuration setup.
l
If an SF123 is to be used as a Check In/Reset station, connect it to any unused point of the room
controller. Be sure and note the point that it is connected to, so it can be correctly programmed
during configuration setup. For more information about check in, see
Check In on page 30
.
SF125 Duty Station:
SF125 stations are installed on 2-gang or 3-gang mounting rings or backboxes.
Connect the red lead from the SF125 LED panel to the positive terminal of the desired point on the
room controller and connect the black wire to the negative terminal of the desired point on the room con-
troller.
Make sure the wires from the toner module and the data/LED module are not wrapped
around each other
. This may cause data issues.
Connect the SF125 Toner Module to a separate point on the same room controller. Connect the
+12V
post to the positive terminal of the desired point, and connect the
Return
post to the negative terminal
of the desired point on the room controller.
If possible, connect the SF125 LED panel to
Point 1 (Purple and Purple/White wires)
, and the toner
module (PM578SM) to
Point 6 (Green and Green/White wires)
. These are the default point connections
for a room controller set up with the duty station preset.
PM123
Auxiliary
Input
Module:
Remove
the
top
cover
from
the
PM123
case.
Inside,
note
the
PM123
harness
and
six
wires.
Connect
the
wiring
from
the
room
controller
and
switches
to
the
PM123
Module.
Connect
the
positive
terminal
of
the
desired
point
on
the
room
controller
to
the
Send
terminal,
and
connect
the
negative
point
of
the
desired
point
to
the
Return
terminal.
If
possible,
connect
the
PM123
Module
to
point
5,
which
is
the
default
connection
point
for
the
PM123.
Connect
the
normally
open
dry
contact
to
be
monitored
to
Contact
1
or
Contact
2
.
There
are
three
available
functions
for
the
PM123
in
the
Config
Tool,
Aux
Input
1
(with
A
and
B
sides),
Aux
Input
2
(with
A
and
B
sides),
and
Aux
Check
In
.
Figure 9 - PM123 Connections
18
|
IL992 Tek-CARE120 Installation Manual
Copyright
©
TekTone Sound and Signal Mfg., Inc. All Rights Reserved