Changing Station Names
Next, change the default station names to names that make sense for the facility.
Note:
The default station names are a combination of the CE module address, the port
number that a room controller is connected to, and the DIP switch address of the room con-
troller. The CE module address provides the first two digits of the default station name
(01-75), and the address of the room controller provides the second two digits (00-63).
If the room controller is connected to port 0A or 0B, only the address of the room controller is used. If
the room controller is connected to port 1A or 1B, add 32 to the address of the room controller to obtain
the last two digits of the default station name.
For example, a room controller addressed as 12 connected to port 0A or 0B of CE 01 would be assigned
a default station name of 0112. If the same room controller (address 12) were connected to port 1A or 1B
of CE 02, it would be assigned a default station name of 0244.
Using the notes generated during system installation, change the default stations names to those desired
by the facility.
Begin by selecting
Stations
in the page selection pane of the Config Tool software. Choose the first sta-
tion you wish to edit, then click the
Edit
button in the upper right corner of the
Stations
pane. The pane
will unlock for editing.
Select the default station name and delete it. Type a new name in place and click
Apply
.
Repeat for all remaining stations to be customized.