MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company Sn-4 – Sn-11
Parameter Summary
Cont.
Function
Parameter
No.
Name
LCD display
(English)
Description
Factory
Setting
Ref.
Operation
Control
Mode
Selection
Sn-04
Run Source
Selection
Sn-04= 0
Run source
Operator
Run source
0: Operator
1: Control terminal
2: RS-485 communication
0
Sec.
9.2.3
Sn-05
Frequency Command
Selection
Sn-05= 0
Ref. Cmd.
Operator
Frequency Command
0: Operator
1: Control circuit terminal
2: RS-485 communication
3: Pulse input
Sn-06
Stopping
Method
Selection
Sn-06= 0
Dec. Stop
0: Deceleration to Stop
1: Coast to Stop
2: Total_range braking stop
3: Coast to Stop with Timer
(Restart after time Bn-02)
Sn-07
Priority of Stopping
Sn-07= 0
Stop Key
Valid
When operation command is from
control terminal or RS-485
communication port
0: operator stop key effective
1: operator stop key not effective
Sn-08
Prohibition of REV
Run
Sn-08= 0
Allow
Reverse
0: reverse run enabled
1: reverse run disabled
Sn-09
Output Frequency
Up/Down Function
Sn-09= 0
Inhibit
UP/DOWN
0: Reference frequency is changed
through pressing the ”UP/DOWN”
key, and then followed by
pressing the “EDIT/ENTER” key.
1: Reference frequency will be
changed immediately after the
”UP/DOWN” is pressed.
Sn-10
Frequency Command
Characteristics
Selection
Sn-10= 0
Ref. Cmd.
Fwd. Char.
0: Reference command has forward
characteristics
(0-10V or 4-20mA / 0-100%
1: Reference command has reverse
characteristics
(10-0V or 20-4mA / 0-100%)
Sn-11
Scanning Times at
Input Terminal
Sn-11= 0
Scan Time 5
ms
0: Scan and confirm once per 5 ms
1: Continuously scan and confirm
twice per 10 ms
Cont.