(4)
In Fig. 4.1.1b the control boards referenced have a jumper TP2 that can select the digital input to terminals
-
to be set for SINK or SOURCE. The following Fig. 4.2.3 (a.) – (d.) show examples for the various
SINK / Source interfaces.
24VG
Sink
Source
24VG
Sink
Source
NPN
+24V
Input Digital
Terminals 1 - 8
Input Digital
Terminals 1 - 8
(a.) Open Collector Interface
(b.) NPN Sensor Interface
Sink Configuration
+24V
Sink
Source
Input Digital
Terminals 1 - 8
(c.) Open Collector Interface
Source Configuration
(d.) PNP Sensor Interface
24VG
Sink
Source
PNP
+24V
Input Digital
Terminals 1 - 8
TP2
TP2
TP2
TP2
Fig. 4.2.3 Sink / Source Configurations
(5)
The MA7200 PLUS inverter has a built-in PG (Encoder) interface and no external PG feedback option card is
required. An external DC source of +12V is required to provide power to the PG.
The following Fig.4.2.4 shows the wiring required for the PG interface.
Cont.