MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company P2-08 – P3-16 Parameter Summary
Function
Parameter
No.
Name
LCD display
(English)
Setting range
Factory
Setting
Ref.
External
PID
Control
P2-08
External PID Set
Point Integral Gain
P2-08
Ext. PID I Time
0.00 - 100.00 s
10.00 s
Sec.
9.2.4
&
APP-1
P2-09
External PID Set
Point Derivative Gain
P2-09
Ext. PID D Time
0.00 - 1.00s
1.00 s
P2-10
External PID Bias
P2-10
Ext. PID Bias
-100 -100%
0%
Load Loss
P3-01
Load Loss Detection
Level
P3-01
Load Loss Det. Level
000 - 200%
030%
Sec.
9.2.4
&
APP-2
P3-02
Load Loss Detection
Time
P3-02
Load Loss Det. Time
00.0 - 25.5s
05.0s
P3-04 Load
Loss
Action
P3-03
Load Loss Action
0: None
1: Load Loss Alarm
2: Load Loss Fault
0
Feedback
P3-04
P3-04
Over Feedback Level
* 000.00 - 099.99%
000.00%
P3-05
P3-05
Over Fbk. Delay Time
0000.0 - 6000.0s
0003.0s
P3-06
Over Feedback
Action
P3-06
Over Fbk. Action
0: None
1: Over Feedback
Alarm
2: Over Feedback
Fault
0
P3-07
Low Feedback Level
P3-07
Low Feedback Level
* 000.00 - 099.99%
000.00%
P3-08
Low Feedback Delay
Time
P3-08
Low Fbk. Delay Time
0000.0 - 6000.0s
0003.0s
P3-09
Low Feedback Action
P3-09
Low Fbk. Action
0: None
1: Low Feedback
Alarm
2: Low Feedback
Fault
0
Suction
P3-10
Low Suction
Detection
P3-10
Low Suction Detect
1: PID Error
2: Current
3: Error and Current
1
P3-11
Low Suction
Detection Time
P3-11
Low Suc. Det. Time
000 - 300s
100s
P3-12
Low Suction PID
Error
P3-12
Low Suc. PID Error
01 - 30%
10%
P3-13
Low Suction Current
P3-13
Low Suction Current
000.1 - 200.0A
001.0 A
P3-14
Low Suction Action
P3-14
Low Suction Action
0: None
1: Low Suction Alarm
2: Low Suction Fault
3: Fault and Restart
1
Restart
P3-15 Restart
Delay
P3-15
Restart Delay
0005 – 6000s
0300s
P3-16 Restart
Selection
P3-16
Restart Selection
0: With Speed
Search
1: W/O Speed
Search
1
* The engineering units and range are set by parameter P1-01
Cont.