MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company App-2 Fan and Pump
Step 4
- Check Fan or Pump Motor Operation
Enter
10.00Hz
for the frequency reference and set parameter
Sn-08 = 1
to disable Reverse Direction operation.
Note
:
The output from the inverter is displayed in
Hz
as factory default. If desired, the output may be displayed in other
units
such as (%) of full speed, or
engineering
units such as PSI etc.
Freq. Cmd 0
0
0.00Hz
TECO
To set the output frequency
to
10.00 Hz
;
key
Flashing
Freq. Cmd 0
1
0.00Hz
TECO
1 - Press the
RESET
key twice
Keypad Steps
Resulting Display
2 - Press the
Flashing
EDIT
ENTER
key to
save
.
3 - Press the
Entry Accepted
2 Seconds
Flashing
Freq. Cmd 0
1
0.00Hz
TECO
NOTES
Cont.