MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company P1-01 –P2-07 Parameter Summary
Table 9.1.4 P
□
-
□□
Application Parameters
(The P parameters were developed mainly for fan and pump applications.
“App-2 Fan and PUMP Application Note”
covers this subject and details the use of these and other parameters.)
Function
Parameter
No.
Name
LCD display
(English)
Setting range
Factory
Setting
Ref.
Engineering
Unit
P1-01
Engineering Unit
Selection
P1-01
Engineering Unit
00 - 25
00
(Set by Cn-28)
Sec.
9.2.4
&
APP-1,
APP-2
Maximum
Feedback
P1-02
Maximum Feedback
Selection
P1-02
Feedback Maximum
10 - 9999
(Engineering Units set
by P1-01)
0
Local /
Remote
P1-03
Local / Remote Key
P1-03
Local / Remote Key
0: Enabled
1: Disabled
0
Sleep
Function
P1-04
Sleep Function
Enable / Disable
P1-04
PID Sleep Function
0: PID Sleep Invalid
1: PID Sleep Valid
0
P1-05
PID Wakeup
Direction
P1-05
PID Wakeup
Direction
0: Feedback above
1: Feedback below
1
External
PID Control
P1-06
External PID
Function
P1-06
Ext. PID Function
0: Ext. PID Invalid
1: Ext. PID, AO1
output
2: Ext. PID, AO2
output
0
Sec.
9.2.4
&
APP-1
P1-07
External PID Set
Point Source
P1-07
Ext. PID Set Source
0: Set Point
Parameter
1: Terminal VIN
2: Terminal AIN
3: Terminal AUX
4: Set Point RS-485
0
P1-08
External PID Set
Feedback Source
P1-08
Ext. PID Fbk. Source
1: Feedback Term.
VIN
2: Feedback Term.
AIN
3: Feedback Term.
AUX
3
P1-09
External PID Set
Point Integral Limit
P1-09
Ext. PID I Limit
1 - 100%
100%
P1-10
External PID Filter
Time
P1-10
Ext. PID Filter
0.0 - 2.5s
0.0s
Sleep
Function
P2-01
Sleep Start Level
P2-01
Sleep Start Level
000.00 - 100.00%
000.00%
Sec.
9.2.4
&
APP-2
P2-02 Sleep
StartDelay
P2-02
Sleep Start Delay
000.1 - 600.0 s
0001.0 s
P2-03
Sleep Wakeup Level
P2-03
Sleep Wakeup Level
000.00 - 099.99%
000.00%
P2-04
Sleep Wakeup Delay
P2-04
Sleep Wakeup Delay
000.1 - 600.0 s
001.0 s
External
PID Control
P2-05
External PID Set
Point Range
P2-05
Ext. PID Set Point
0.0 - 100.0%
0.0%
Sec.
9.2.4
&
APP-1
P2-06
External PID Set
Point Feedback Gain
P2-06
Ext. PID Fbk. Gain
0.01 - 10.00
1.00
P2-07
External PID Set
Point Proportional
Gain
P2-07
Ext. PID P Gain
0.01 - 10.00
1.00
Cont.