MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company P2-08
cont.
– P2-10 Parameter Details
Table 9.2.4.4b
Terminals available for external PID while (main) PID is
ENABLED
(Sn-64
≠
0)
Sn-05
Setting
Sn-24
Setting
Sn-29
Setting
Terminals
Available to Ext.
PID
Comment
1
0
9
*
AIN (0/4-20mA)
VIN is used as main PID feedback
AUX is used as main PID set point
1
9 VIN
(0-10V)
AIN is used as main PID feedback
AUX is used as main PID set point
≠
9
AUX (0-10V)
AIN is used as main PID feedback
VIN is used as main PID set point
2 or 3
9
*
None
(External PID is
unavailable)
VIN and AIN are used as main PID feedback
AUX is used as main PID set point
0, 2, or 3
0
-----
AIN, AUX
VIN is used as main PID feedback
1 VIN,
AUX
AIN is used as main PID feedback
2 or 3
AUX
VIN and AIN are used as main PID feedback
*Terminal VIN is used as the main PID feedback and Sn-29 must equal 9 to set terminal AUX as the main PID set
point, otherwise an error message will be displayed.
If the AUX input is selected for use by the External PID Functions (P1-07=3) or (P1-08=3), Sn-29 will be set to 18
(Ext PID Set point) or 19 (Ext PID Feedback) automatically, and can not be edited until input AUX is not selected
as an External PID Function Source.
The following parameters pertain to the external PID function gain settings and monitoring.
P1-09
PID Integral (I) limit (Cannot change during operation)
P1-09 Range: 1 – 100%
P1-10
PID filter time constant (Cannot change during operation)
P1-10 Range: 0.0 – 2.5 sec.
P2-05
PID set point value (Can change during operation)
P2-05 Range: 0.0 – 100.0%
P2-06
PID feedback gain (Can change during operation)
P2-06 Range: 0.01 – 10.00
P2-07
PID proportional gain (P) (Can change during operation)
P2-07 Range: 0.01 – 10.00
P2-08
PID Integration (I) time (Can change during operation)
P2-08 Range: 0.00 – 100.00 sec.
P2-09
PID derivative (D) time (Can change during operation)
P2-09 Range: 0.00 – 1.00 sec.
P2-10
PID bias (Can change during operation)
P2-10 Range: -100 – 100%
Cont.