MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company P1-03 - P2-04
cont.
– P1-07 Parameter Details
][
P1-03
Local / Remote Key (0 -1)
P1-03=0: Local / Remote key is enabled.
1: Local / Remote key is disabled.
(When disabled this key is used as a JOG key)
When P1-03 is enabled, the local / remote function is effective when the inverter is in
stop
mode. Below is a list
of Run Source, Frequency Source, SEQ LED Status, and REF LED Status during Remote Mode and Local Mode.
Status
Run command source
and frequency command source
SEQ LED Status
REF LED Status
Remote
Set by parameters Sn-04, Run
Source Selection and Sn-05,
Frequency Source Selection.
ON if Sn-04 is not 0
(Run source is
not from keypad)
ON if Sn-05 is not 0
(Frequency source is
not from keypad)
Local From
keypad
OFF
OFF
When P1-03 is enabled, the inverter is in remote mode after power-on and the Local / Remote switch is effective
only when the inverter is in stop mode.
Generally, the local / remote switch is used when Sn-04 and Sn-05 = 0 at the same time (
either the RUN source
or Frequency source is controlled by the keypad
). The local / remote function is disabled if both Sn-04 and Sn-05
are set to 0.
When P1-03 is disabled, the Local / Remote key operates as a JOG key. The JOG function is effective if:
1 -The inverter is in stop mode and
2 - Sn-04 = 0 (Run source is from the keypad).
The following parameters pertain to the sleep function.
P1-04
PID sleep function (0 -1)
Cannot be changed during operation.
P1-04=0: PID function invalid
1: PID function valid
If the PID function is
disabled
, Sn-64 = 0, and the parameter P1-04 PID Sleep Function is set to 1 (PID Sleep Valid),
a
"PID Sleep Setting Error"
will occur.
P1-05
PID wake up direction (0 -1)
Cannot be changed during operation.
P1-05=0: Feedback above
1: Feedback below
P2-01
Sleep start level (000.00 – 100.00%)
Can be changed during operation.
P2-02
Sleep start delay (000.1 – 600.0sec.)
Can be changed during operation.
P2-03
Sleep wake up level (000.00 – 099.99%)
Can be changed during operation.
P2-04
Sleep wake up delay (000.1 – 600.0sec.)
Can be changed during operation.
Figs. 9.2.4.2a and 9.2.4.2b below show a block diagram and a graph illustrating the sleep function.
Fig. 9.2.4.2a PID Sleep Function Block Diagram
Cont.