10-13
LED display
Description
Cause
Possible solutions
External
Terminal Stop
Error
External Terminal is main run
command source selection
(00-02=1) and run command
executes but executes stop
command from keypad.
Run command executes
from external terminal but
executes stop command
from keypad.
Remove the run command
from external terminal
ADC Voltage
Error
Abnormal voltage level on the
control board
Abnormal input voltage, too
much noise or
malfunctioning control
board.
Check the input voltage
signal and the voltage on
the control board.
EEPROM
Archiving Error
EEPROM Poor archiving
EEPROM poor peripheral
circuit
It occurs in parameters
check at inverter boot.
Reconnect and if the
warning signal appears
again, replace the circuit
board.
Contact TECO for more
information.
Control Board
Error
The control board is not
correspondent with the
program.
The control board is not
correspondent with the
program.
Replace the control
board.
Wrong running
direction Error
Only for run in one direction,
another direction command is
not allowed.
Run command for another
direction on the terminal of
control board is active.
Cancel the run command
for another direction on
the terminal of control
board.
PTC Signal
Loss
PTC Signal Loss detecting
triggers error message
PTC connection trips and
has lasted for more than
10 seconds.
Check if MT terminal and
GND terminal are
connected.
Parameters
Locked
Parameter password have
been locked
Parameter password
function (13-07) starts.
Correct password input at
parameter 13-07
Password
Setting Error
Password input at the second
time is different from that at
the first time when the
password lock function
enables.
Password input at the
second time is different
from that at the first time
when the password lock
function enables
.
Password input at the
second time is the same
as that at the first time
when the password lock
function enables.
Operator
Reading Error
Operator cannot read the
inverter’s information.
Since signals from the
inverter
’s control board are
transmitted error, the
inverter cannot normally
transmit the data to
operator.
Check if the inverter is
normally connected to the
operator.
RDE*
Содержание F510 Series
Страница 1: ......
Страница 42: ...3 31 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 46: ...3 35 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 282: ...4 210 Frequency 1 11 72 Frequency 2 11 73 Output Frequency 11 69 Gain of Preventing Oscillation 3 0 ...
Страница 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...
Страница 444: ...Ver 02 2019 09 ...