4
-
128
Value
Function
Description
Control mode
Name
LCD Display
V/F SLV
PM
SLV
7
Stall Prevention Level
During Running
Run Stall Level
Adjust the action level (30% ~
200%) of stall prevention in
operation based on analog input.
The inverter rated current =100%
O
X
O
8
Frequency Lower Limit
Ref. Low Bound
Adjust the lower limit (0 ~ 100%)
of frequency command based on
analog input, the maximum output
= 100%. The lower limit of
frequency command is the greater
one of the actual frequency
command’s lower limit 00-13 or
the multi-function analog input.
O
O
O
9
Jump Frequency 4
Jump Freq 4
Jump frequency 4.
100% = maximum output
frequency
O
O
O
10
Added to AI1
Add to AI1
Added to AI1.
100% = maximum output
frequency
O
O
O
11
Positive Torque Limit
Positive Tq Limit 100% = M
otor’s rated torque
X
O
O
12
Negative Torque Limit
Negative Tq Limit 100% = M
otor’s rated torque
X
O
O
13
Regenerative Torque
Limit
Regen. Tq Limit
100% = M
otor’s rated torque
X
O
O
14
Positive / Negative
Torque Limit
+/- Tq Limit
100% = M
otor’s rated torque
X
O
O
15
Torque Limit
Tq Limit
100% = M
otor’s rated torque
X
X
X
16
Torque Compensation Tq Compensation 100% = M
otor’s rated torque
X
O
X
17
Reserved
No Function
Reserved
O
O
O
Note: When the setting of AI2 and AI3 are the same, use AI2 signal only.
04-05=0:
Auxiliary frequency
When parameter 00-05 = 1 (main frequency from external control) the auxiliary speed reference frequency
can be activated via the multi-speed input commands (see table 4.3.5). The auxiliary frequency command
can be set via AI2
/AI3
. The maximum output frequency is set by 01-02, Fmax =100%.
04-05
/04-10
=1:
Frequency Reference Gain (FGAIN)
Multi-function analog input AI2
/AI3
can be used to adjust the frequency reference gain of analog input AI1.
The total frequency reference gain of terminal AI1 is the internal gain set by parameter 04-02 times FGAIN.
The maximum frequency reference for AI1 is 100%.
100%
-10V
+10V
(20mA)
0V
(4mA)
FGAIN
Terminal AI2
analog input
Figure 4.3.28 Frequency gain adjustment
Example:
When the internal gain of AI1 (04-02) is set to 100% and AI2 to 5V (for example FGAIN = 50%), the
reference frequency of terminal AI1 will be 50%, as shown in Fig. 4.3.29.
Содержание F510 Series
Страница 1: ......
Страница 42: ...3 31 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 46: ...3 35 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 282: ...4 210 Frequency 1 11 72 Frequency 2 11 73 Output Frequency 11 69 Gain of Preventing Oscillation 3 0 ...
Страница 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...