3-42
(C)
Grounding:
(1)
Connect the ground terminal (E) to ground having a resistance of less than 100Ω.
(2)
Do not share the ground wire with other devices, such as welding machines or power tools.
(3)
Always use a ground wire that complies with the local codes and standards for electrical
equipment and minimize the length of ground wire.
(4)
When using more than one inverter, be careful not to loop the ground wire, as shown below
in Fig. 3.3.6.2.
F510
F510
F510
F510
F510
F510
a) Correct
b) Correct
F510
F510
F510
c) Incorrect
Loop
Figure 3.3.6.2 F510 Inverter Grounding