4-103
03-0X =63
: Switch to Tolerance Range of Constant Pressure 2
When using in PUMP mode (23-00=1), the tolerance range of constant pressure (23-09) will be used for
waking up the inverter. When digital input terminal enables, the tolerance range of constant pressure 2
(23-34) will be used.
03-0X =65:
Short-circuit breaking
To stop inverter by turning on Short-circuit breaking with setting terminal. If executing run command or jog
command, short-circuit breaking command will erased and start to run. The following picture is short-circuit
breaking time process.
Note:
Either short-circuits braking command or DC braking command is selected. If these two modes are
both selected, SE02 error (DI Terminal Error) will occur.
Short
Circuit
Brake
Short
Circuit
Brake
t
01-08
(Fmin)
The larger of 01-08
or 07-06
Run
Command
Short Circuit
Braking
Command
Output
Frequency
(or Jog command)
OFF
ON
OFF
ON
t
t
03-0X =68:
External Fault 2
‧
When an external fault occurs, the external fault 2 input terminal is turned on, the inverter will be turned
off and the motor will free run to stop.
‧
If external input terminal S3 is set (03-
02 = 68) as external fault, the message “EF3 Ext. Fault (S3)”
(EF3) will be displayed.
‧
All six input terminals (S1 to S6) can be designated as external fault input.
03-0X =69:
External Overload, Input Terminal is Normally Closed Switch.
‧
When external overload occurs, the external overload input terminal closed, the inverter will be turned
off and the motor will decelerate to stop.
‧
If the external input terminal S5 is set (03-
04 = 69) to external overload, “TOL Ext. OverLoad” message
will be displayed.
‧
To enable the external overload function, the fire mode must be enabled first (08-48 =1), only the
external input terminal S5 can be designated as External Overload Input.
‧
Setting the external input terminal as External Overload will set the input terminal as the normally
closed, therefore, before setting the external overload function, do not set the operation command from
the external terminal, otherwise, it will cause unnecessary damage.
03- 08
(S1~S6) DI Scan Time
Range
【
0
】
Scan Time 4ms
【
1
】
Scan Time 8ms
Set the digital input CPU scan time. The digital input signal needs to be present for the minimum scan time
to qualify as an enabled command.
Note:
For noisy environments select scan time of 8ms (results in a slower response time).
Содержание F510 Series
Страница 1: ......
Страница 42: ...3 31 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 46: ...3 35 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 282: ...4 210 Frequency 1 11 72 Frequency 2 11 73 Output Frequency 11 69 Gain of Preventing Oscillation 3 0 ...
Страница 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...
Страница 444: ...Ver 02 2019 09 ...