4
-
264
error signal of OPbFt when the stop time ends.
Note:
When user does not want the inverter to be restricted by the maximum pressure, set 23-74=0
(disable) to disable the function of high pressure limit.
Figure 4.4.107 Diagram for warning to stop at high pressure limit
23- 74
High Pressure Setting
Range
【
0
】
Disable
【
1
】
High Pressure Warning
【
2
】
High Pressure Warning or Error
When 23-74=0, High pressure warning or error is disabled.
When 23-74=1, High pressure warning is enabled. High pressure error is disabled.
When 23-74=2, High pressure warning or error is enabled. Refer to the instruction of Fig. 4.4.107.
23- 16
Warning Time of Low Pressure
Range
【
0.0 ~ 600.0
】
Sec
When pressure feedback value is lower than minimum pressure limit, warning time of low pressure starts
to count. If pressure feedback value is higher than minimum pressure limit during counting time, the
warning time will recount and the inverter will display the warning signal of LoPb when the warning time
ends.
23-12 Maximum Pressure Limit
Bar
23-02 Target Pressure Value
23-15 Minimum Pressure Limit
Pressure Feedback Output
Stop along the deceleration time (00-15)
time
time
Hz
HIPb
T1 < (23-13); Recounting after T1
T2 = (23-13); Keypad flashes and displays HIPb
T3 = (23-14); Keypad flashes and displays OPbFt
T1
T2
T3
OPbFt
Содержание F510 Series
Страница 1: ......
Страница 42: ...3 31 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 46: ...3 35 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 282: ...4 210 Frequency 1 11 72 Frequency 2 11 73 Output Frequency 11 69 Gain of Preventing Oscillation 3 0 ...
Страница 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...
Страница 444: ...Ver 02 2019 09 ...