4
-
206
- The hold function at stop is inactive when the hold frequency at stop (11-45) is set to a value less than
Fmin (01-08).
11- 47
KEB Deceleration Time
Range
【
0.0~25.5
】
Sec
11- 48
KEB Detection Level
Range
200V :
【
190~210
】
V
400V :
【
380~420
】
V
KEB function can be used to keep the inverter from tripping on a under voltage condition due to a
momentary power-loss. To enable the KEB function set parameter 11-47 to a value greater than 0.0 sec.
Upon detection of a power-loss the inverter uses the KEB deceleration time (11-47) to decelerate the
motor and using the regenerative energy from the motor to maintain the DC-bus at a nominal level.
11-48: KEB detection level
If the DC-bus voltage falls below the value set in 11-48, the KEB is activated and the inverter starts
decelerating according to the value set in 11-47.
To accelerate back to the original output frequency one of the digital inputs (03-00 to 03-05) set for 48
(KEB acceleration) has to be activated and the DC voltage has to rise above 11-48 + delta V (Delta V =
+10V for 200V series, Delta V = +20 V for 400V series).
Refer to the example in Fig.4.3.83.
DC Bus
KEB Detection Level
10V for 200V series
20V for 400V series
Output
Frequency
Run
Command
KEB
Re-acceleration
Command
Re-acceleration
KEB
operation
Figure 4.3.83 KEB operation
Содержание F510 Series
Страница 1: ......
Страница 42: ...3 31 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 46: ...3 35 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 282: ...4 210 Frequency 1 11 72 Frequency 2 11 73 Output Frequency 11 69 Gain of Preventing Oscillation 3 0 ...
Страница 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...
Страница 444: ...Ver 02 2019 09 ...