4
-
260
23- 05
Display Mode Selection
Range
【
0
】
: Display of Target and Preesure Feedback
【
1
】
: Only Display Target Pressure
【
2
】
: Only Display Pressure Feedback
This function can have the common display of target and feedback pressure or display separately.
when 23-05=0000
:
Led keypad displays pressure setting value and pressure feedback value.
Two-digit in the left is the pressure value setting and two-digit in the right is the pressure feedback value
in the seven-segment monitor.
Note:
When 23-00=2 (HVAC), the unit will be multiplied by 1000 times. If the display value is 5.0, it
means 5000GPM (It is only displayed in inverter software V1.4.)
when 23-05=0001
:
Led keypad only displays the pressure setting value.
when 23-05=0002
:
Led keypad only displays the pressure feedback value.
Notes:
-
Once the target value is bigger than 10, the target value is only shown as "an integer" instead of "a
decimal." 10-33 is lower than 1000 and 10-34=1 in the PID modes.
- If Pump mode is used in inverter software V1.3, parameter 23-03 is required to set to <= 9.9 PSI.
23- 06
Proportion Gain (P)
Range
【
0.00~10.00
】
23- 07
Integral Time (I)
Range
【
0.0~100.0
】
Sec
23- 08
Differential Time (D)
Range
【
0.00~10.00
】
Sec
Содержание F510 Series
Страница 1: ......
Страница 42: ...3 31 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 46: ...3 35 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 282: ...4 210 Frequency 1 11 72 Frequency 2 11 73 Output Frequency 11 69 Gain of Preventing Oscillation 3 0 ...
Страница 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...
Страница 444: ...Ver 02 2019 09 ...