24-00=4: in the cycle modes of inverter pump, first on and first off; then stop all.
All the motors besides the pump are drived by the inverter and switching off the pump (motor) is by the
sequence of the first on.
24-00=5: only inverter pump stops in the cycle modes of inverter pump.
When the inverter sends the stop command, only the pump (motor) stops but the Relay keeps on.
24-00=6 :
1 to 3 Relay of Cycle Modes of Inverter Pump: First on and First off; then Stop All.
This mode runs via a Relay with a pump in the cycle modes of inverter pumps. If 24-07=1, only Relay in
the control board is enabled in 1 to 3 Relay of cycle modes and can switch the drive sequence of every
pump.
24-00=7: Cycle Modes of Inverter Pump: First on and First Off; then Stop All. And First Boot Relay
in Cycling.
The first inverter drives the motor depending on the Relay switching time (24-
08) to change the inverter’s
position.
24-00=8:
Cycle Modes of Inverter Pump 1 to 3 Relay: First on and First Off; then Stop All. And First
Boot Relay in Cycling.
The inverter drives the motor at the first time depending on the Relay switching time (24-08) to change the
inverter’s position. That is, at this mode, the inverter runs in a Relay with a pump. Users can switch the
orders of each pump driving at this cycle mode of 1 to 3 Relay with the setting of parameter 24-07.
24-00=9
:
Cycle Modes of Inverter Pump 1 to 3 Relay: Only Stop Inverter Pump. And First Boot
Relay in Cycling.
As the fixed modes, first on and first off, but only stop the inverter pump. The inverter drives the motor at
the first time depending on the Relay switching time (24-
08) to change the inverter’s position. (The Relay
switching is enabled only in one motor.)
Notes:
- When 1 to 8 pump card is not installed, it is forced to be disabled (24-00=0).
- When parameter 24-00 (pump control selection) is enabled, the selection of DI function to 16 (PID
function disable) and 57 (forced frequency run) are disabled.
- Set 24-07=1 to enable the Relay in the control board to provide the function selection of 1 to 8 pump
cards, or it is still forced to be disabled.
- 1 to 8 pump cards enabled or disabled and the selection modes of water supply are determined by
parameter 24-00.
- PID Setting:
PID function is enabled via the setting of PID control mode (10-03) to xxx1b (PID enable). Set PID
target value source (10-00) to 4 (10-02 given) and the target value is determined by 10-02. If the
feedback value source (10-01) is set to 2 (AI2 given) and AI input signal type (04-00) is set to 0 (AI2:
0~10V), it requires
to set the dip switch
to V in the control board.
Содержание F510 Series
Страница 1: ......
Страница 42: ...3 31 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 46: ...3 35 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 282: ...4 210 Frequency 1 11 72 Frequency 2 11 73 Output Frequency 11 69 Gain of Preventing Oscillation 3 0 ...
Страница 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...
Страница 444: ...Ver 02 2019 09 ...