4
-
136
Table 4.3.9
Selection of analog output terminals function
(04-11 and 04-16)
04-11, 04-16
Parameter setting
Function
(Keypad display)
Monitoring Parameters
Group 12
Control Mode
VF
SLV
PM
SLV
0
Output Freq
12-17
O
O
O
1
Freq Ref
12-16
O
O
O
2
Output Voltage
12-19
O
O
O
3
DC Voltage
12-20
O
O
O
4
Output Current
12-18
O
O
O
5
Output KW
12-21
O
O
O
6
Motor Speed
12-22
O
O
O
7
Output PF
12-23
O
O
O
8
AI1 Input
12-25
O
O
O
9
AI2 Input
12-26
O
O
O
10
Torque Ref
12-27
X
O
O
11
Current Iq
12-28
X
O
O
12
Current Id
12-29
X
O
O
13
Speed Deviation
12-30
X
O
O
14
Reserved
-
X
X
X
15
ASR Output
12-32
X
X
X
16
Reserved
-
X
X
X
17
Voltage Ref Vq
-
X
O
O
18
Voltage Ref Vd
-
X
O
O
19~20
Reserved
-
X
X
X
21
PID Input
12-36
O
O
O
22
PID Output
12-37
O
O
O
23
PID Setpoint
12-38
O
O
O
24
PID Feedback
12-39
O
O
O
25
Output Freq (SFS)
-
O
O
O
26~27
Reserved
-
X
X
X
28
Comm Control
-
O
O
O
04-20
Filter Time of AO Signal Scan *1
Range
【
0.00~0.50
】
Sec
*1: It is new added in inverter software V1.12.
This function is used for filtering out momentary change of analog output signal.
Note: When this function is added, it will decrease the system reaction but increase interference
protection.
Содержание F510 Series
Страница 1: ......
Страница 42: ...3 31 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 46: ...3 35 200V 150 175HP 400V 300 425HP Terminal screw size T M12 M10 400V 530 800HP Terminal screw size T M10 M10 ...
Страница 282: ...4 210 Frequency 1 11 72 Frequency 2 11 73 Output Frequency 11 69 Gain of Preventing Oscillation 3 0 ...
Страница 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...
Страница 444: ...Ver 02 2019 09 ...