22
5.2.6 Input and output wire selections
Select circuit breaker and cable size as per table
Servo Stabilizer Input & Output Cable requirement cha rt
Input Operating Range
(360-460) VAC
Output
415 VAC +/-1%
KVA
Input Details
Input Breaker
Output Details
Output Breaker
3P+N
Current(A)
Cable
(Sqmm)
MCB/MCCB (3P)
Current(A)
Cable (Sqmm)
MCB/MCCB (3P)
7.5
12.50
1.5
16A
10.87
1.5
16
10
16.67
2.5
20A
14.49
2.5
16
15
25.00
6
32A
21.74
6
32
20
33.33
10
40A
28.99
10
32
25
41.67
10
50A
36.23
10
40
30
50.00
16
63A
43.48
16
50
40
66.67
25
80A
57.97
25
63
50
83.33
35
100A
72.46
35
80
60
100.00
35
125A
86.96
35
100
70
116.67
50
125A
101.45
50
125
80
133.33
50
150A
115.94
50
125
100
166.67
70
175A
144.93
70
150
125
208.33
95
225A
181.16
95
200
150
250.00
100
300A
217.39
100
300
Table 6 Input and output wire selection table for 360-460VAC Range
Servo Stabilizer Input & Output Cable requirement chart
Input Operating Range
(340-480) VAC
Output
415 VAC +/-1%
KVA
Input Details
Input Breaker
Output Details
Output Breaker
3P+N
Current(A)
Cable
(Sqmm)
MCB/MCCB (3P)
Current(A)
Cable (Sqmm)
MCB/MCCB (3P)
7.5
13.89
1.5
16A
10.87
1.5
16
10
18.52
2.5
20A
14.49
2.5
16
15
27.78
6
32A
21.74
6
32
20
37.04
10
40A
28.99
10
32
25
46.30
10
50A
36.23
10
40
30
55.56
16
63A
43.48
16
50
40
74.07
25
80A
57.97
25
63
50
92.59
35
100A
72.46
35
80
60
111.11
50
125A
86.96
35
100
70
129.63
50
125A
101.45
50
125
80
148.15
50
150A
115.94
50
125
100
185.19
70
175A
144.93
70
150
125
231.48
95
225A
181.16
95
200
150
277.78
120
300A
217.39
100
300
Table 7Input and output wire selection table for 340-480VAC Range