23
Servo Stabilizer Input & Output Cable requirement chart
Input Operating Range
(280-520) VAC
Output
415 VAC +/-1%
KVA
Input Details
Input Breaker
Output Details
Output Breaker
3P+N
Current(A)
Cable
(Sqmm)
MCB/MCCB (3P)
Current(A)
Cable (Sqmm)
MCB/MCCB (3P)
7.5
16.67
2.5
20A
10.87
1.5
16
10
22.22
4
32A
14.49
2.5
16
15
33.33
10
40A
21.74
6
32
20
44.44
10
50A
28.99
10
32
25
55.56
16
63A
36.23
10
40
30
66.67
16
80A
43.48
16
50
40
88.89
35
100A
57.97
25
63
50
111.11
50
125A
72.46
35
80
60
133.33
50
150A
86.96
35
100
70
155.56
70
175A
101.45
50
125
80
177.78
70
200A
115.94
50
125
100
222.22
95
225A
144.93
70
150
125
277.78
95
300A
181.16
95
200
150
333.33
120
350A
217.39
100
300
Table 8 Input and output wire selection table for 280-520VAC Range
5.2.7 Connection of input terminals
As this is an equipment with class I protection against electrical shocks, it is essential to
install the protection earth conductor (connect earth
). Connect this conductor, before
supplying voltage to the input terminals.
In three phase stabilizers consisting of single phase equipment’s, it is needed and essential to
make one of these two options as regards to the earth
Joint the earth terminals (screws) of the three equipment’s by means of the cable
and connect the protective earth cable coming from the installation to any of the
terminal.
Or come with one separate earth cable to each terminal (screw) of each
equipment, but they have to come from the same point
Depending on the model of stabilizer, the power supply connections are directly done to the
terminals or to the own rods of the input switch or breaker.