background image

24 

 

 

      The illustrations corresponding to models in cabinet are shown with direct connection over the 

maneuvering mechanism as a mere example. Models with no terminals, the connection order 
will not differ from the one stated unless the labelling of the equipment states it 

 

      Connect the power supply cables to input terminals (P) and (N) in single phase equipment’s or 

(R), (Y), (B) and (N) in three phase equipment’s 

 

      

 

In three phase stabilizers consisting of three single phase cabinets, in case it was requested to 

have one single point to connect the neutral, joint the neutral rod of the three equipment’s by 
means of the two extensions copper rods. Otherwise connect the suitable cross cable section 
to the three terminals corresponding to the neutral of each equipment. When it is not  a 
conditioning (only one conductor), it is able to connect a suitable cross cable s ection to the 
input neutral terminal of each equipment. 

 

     

In case of discrepancies between the labelling and the instructions of this manual, the labelling 

will always prevail. 

5.2.8 Connection of output terminals 

 

              

As this is an equipment with class I protection against electrical shocks, it is essential to 

install the protection earth conductor (connect earth

). Connect this conductor, before supplying 

voltage to the input terminals. 

 

Depending on the model of stabilizer, the load or loads  connections are directly done to the 

terminals or to the own rods of the manual switch option, if it is included. 

 

The illustrations corresponding to models in cabinet, are shown with direct connection over the 

manual bypass maneuvering mechanism as a mere example. For those models without this option, 
there will always be a terminal strip. Models with no terminals, the connection order will not differ 
from the one stated unless the labelling of the equipment states it. 

 

Connect the cables to supply the loads or loads to the output terminals and in single phase 

equipment’s or (R), (Y), (B) and (N) in three phase equipment’s, Pay attention to the neutral 
connection in a three phase unit with star configuration, because if the line is connected instead of 
the neutral, the load will suffer a high over voltage that can destroy it. In three phase equipment’s 
with delta output, the neutral terminal (N) is not available.  

 

 In three phase stabilizers consisting of three single phase cabinets, in case it was requested to have 

one single point to connect the neutral, joint the neutral rod of the three equipment’s by means of 
the two extensions copper rods, otherwise connect the suitable cross cable section to the three 
terminals corresponding to the neutral of each equipment. When it is not a conditioning (only one 
conductor), it is able to connect a suitable cross cable section to the output neutral terminal (N) of 
each equipment.  

 

 In case of discrepancies between the labelling and the instructions of this manual, the labelling 

will always prevail.  

 

 With respect to the protection that must be placed at the output of the stabilizer, we recommend 

that the output power should be distributed in four lines, at least. Each one of them should have a 
circuit breaker protection switch of a quarter of the nominal power. This type of output power 
distribution will allow, in the event of a breakdown in any of the machines connected to the 
equipment that causes a short-circuit, will only affect to the line that is faulty. The rest of the 
connected loads will have their continuity assured due to the tripping of the protection of the line 

Содержание TVS-S1

Страница 1: ...TECHNOVISION ENERGY PVT LTD PUNE Servo VoltageStabilizer UserManual ________________________________________________________________________________________________________________________________...

Страница 2: ...T E CH N O V IS IO N E N E R Y P V T L T D ServoVoltageStabilizerUserManual Technovision Energy Pvt Ltd KONARK Narhe Industrial Area Pune 411 041 Phone 20 24390 063 093 84...

Страница 3: ...4 1 1 4 Three phase Oil cooledSeries 7 4 1 1 5 Three phase AircooledPowerConditionerSeries 8 4 2 Presentation 8 4 3 Main qualityperformances 10 4 4 Panel indication controls 11 4 5 Operatingprinciple...

Страница 4: ...Bypassmanual option 27 6 3 1 Load powersupplyfrommainsthroughthe manual Bypass 27 7 Control panel Overview 28 7 1 Board connection 28 7 2 Wiringdiagram 29 7 3 TRIACcard connection 29 7 4 LED indicatio...

Страница 5: ...ectronic components All the parameters have been checked counter checked adequately to ensure long and trouble free service All thepointsmentioned in the operating manual are strictly adhere to You ar...

Страница 6: ...ory being the user the legal responsible regarding to its observance and application Prevent exposure to the elements and do not allow water To enter the Stabilizer Please installed the indoors Avoid...

Страница 7: ...the wiring Risk of electric shock is greater in areas that are wet or damp InstallGround Fault Circuit Breakers ELCB as they willinterrupt the electricalcircuit before acurrent sufficient to cause de...

Страница 8: ...he client s requirements and in the legal and regulations The Quality and Environmental Policy diffusion and the fixation of the Quality and Environment targets To carry out revisions by the Managemen...

Страница 9: ...he ISO 14001 norm 3 4 EQUIPMENT RECYCLING AT THE END OF ITS USEFUL LIFE Our company commits to use the services of authorized societies and according to the regulations in order to treat the whole rec...

Страница 10: ...s consisting of three single phase cabinets each one of them will have their own control panel 4 1 1 1 Single phase Aircooled Stabilizer Model Number KVA Rating Voltage Rating Dimensions L X W X H MM...

Страница 11: ...1000 Table 2 Three phase Air Cooled Stabilizer 4 1 1 3 Three phase Air cooled Series with Isolation Transformer Model Number KVA Rating Voltage Rating Dimensions L X W X H MM Input Output TVS TISO30 2...

Страница 12: ...r Conditioner Series 4 2 PRESENTATION Servo Voltage stabilizer model has been designed to operate in fluctuated mains and to safeguard the critical loads in particular those ones with a complicated na...

Страница 13: ...s no matter if they include some options or not they are supplied assembled in one metallic cabinet and divided in two cabinets joined together mechanically at factory or by three separate cabinets w...

Страница 14: ...t sensors to make the overload measurement As an option the stabilizer can be equipped with a manual Bypass which is not ready to be maneuvered with load connected It allows keeping the loads supplied...

Страница 15: ...ed level between 220V and 240V in each phase in Auto mode Reset auto Manual When the reset switch is in Auto position the Output will available automatically When the Reset switch is in manual positio...

Страница 16: ...to the use of low internal mechanical system PIC 18F4520 continuously monitorthe output voltage with reference voltage and generate error signal Any error voltage is amplified this amplified error vo...

Страница 17: ...windings which provides a high level of electrical noiseattenuation 40dB This option can be built in either inside the TVS TISO series attending to differentoperatingconditioning or in a separate case...

Страница 18: ...se load will be done by Buck Boost Transformer 4 7 2 BUCK BOOST TRANSFORMER Contrary to dimmer it is in rectangular shape Bobbin is fitted with EI CRGO or HRGO core When the transformer structure is b...

Страница 19: ...ARBON BRUSH This is a moving part in servo stabilizer it is fitted in the shaft to make thecontactwithVariac If the input voltage variation is very frequent this carbon brush will erase earlyandcustom...

Страница 20: ...evice is connected in parallelon the stabilizer input power supply circuit this is the most commonly used and most efficient type of ElectricalSpikes Sudden Voltage fluctuation protection 4 7 7 MCB MC...

Страница 21: ...equipment turned Off 5 1 TO CONSIDER IN THE INSTALLATION The equipment s have terminals for its input and output connections Neverthelesssomemodels due to their high power rate the power supply cable...

Страница 22: ...the values are calculates for a maximumcable lengthof 30 m between the protection panels equipment and loads 1 For higher lengths correct the cross sections in order to avoid dropping voltages in acco...

Страница 23: ...been designed to assure the maximumprotectionduringtransportant storage 5 2 3 Unpacking The packaging of the equipment has wooden pallet cardboard or wooden enclosuredepending on the case polystyrene...

Страница 24: ...the stabilizing feet Failure to follow these instructionscanresult in death or serious injury Move to the Installation Site Use a pallet jack or a forklift to move the Modular PDU Make sure to lift on...

Страница 25: ...n will be provided with input protections RCB and circuit breakers sized to the current stated in the nameplate of the equipment at least and characteristicequaltothestated figure in the Recommended i...

Страница 26: ...4 93 70 150 125 208 33 95 225A 181 16 95 200 150 250 00 100 300A 217 39 100 300 Table 6 Input and output wire selection table for 360 460VAC Range Servo Stabilizer Input Output Cable requirement chart...

Страница 27: ...utput wire selection table for 280 520VAC Range 5 2 7 Connection of input terminals As this is an equipment with class I protection against electrical shocks it is essentialto install the protection e...

Страница 28: ...utthisoption there will always be a terminal strip Models with no terminals the connection orderwillnotdiffer from the one stated unless the labelling of the equipment states it Connect the cables to...

Страница 29: ...d or loads to this single point will create back feed loops to earth that will affect to the qualityofthepowersupplied Regardless of the equipment has one or two protection earth terminals are always...

Страница 30: ...switch is 0 OFF Turn the Rotary switch to position 2 Servo In case the switch were at position 1 Mains turn it to position 2 Servo Check that the loads are shutdown 6 2 START UP AND SHUTDOWN OF THE ST...

Страница 31: ...ply from mains through the manual Bypass Shutdown the load and stabilizer as section 6 2 2 states Turn the manual Bypass switch option to position 1 Mains Or Bypass Thestabilizerwillbeout of service a...

Страница 32: ...28 CONTROLPANEL 7 OVERVIEW 7 1 board connections Chapter 7...

Страница 33: ...29 7 2 wiring diagram 7 3 TRIAC connections...

Страница 34: ...v Overload Indication Red LED Ovl Output ON Green LED o p ON 7 5 Running Mode Display 7 6 KEY function Key Set Mode Run Mode HOLD BACK Short Back to previous display Short Change display Hold Freeze d...

Страница 35: ...ght password the display will now show the GENERAL SETTINGSscreenwhichhas three options respectively Error LOG LOG Parameter settings SET Calibration CAL Press the START STOP key to navigate between t...

Страница 36: ...AIL 0 999S ON Delay Auto start delay 0 999S Sensitivity Sensitivity 1 25V Hysteresis Hysteresis 1 25V Auto Man Auto ON after error condition is cleared Auto Manual Phase Rev Phase reverse protection Y...

Страница 37: ...ser enters into this mode and is turned back ON again when the user comes out of this mode and the output is adjusted by the algorithm 7 7 7 Calibration For calibrations select CAL option take pre cal...

Страница 38: ...creen at any moment press the BACK key For returning to the RUN mode from the GENERAL SETTINGS screen press the BACK key Parameter Description Set Values R Ph Vin R phase input voltage calibration Ent...

Страница 39: ...soon as voltage becomes high OFF when the voltage becomes normal Output Low I P Fail OFF OP OFF ON as soon as voltage becomes low OFF when the voltage becomes normal Overload OVL ON OP OFF ON when cro...

Страница 40: ...operly Probably it is required the replacement of the limit switch Prevent any conductive or Inflammable cotton particles from depositing on Veriac surface Check all power wiring nut bolts for tightne...

Страница 41: ...r SR NO Inspection Frequency Items to be inspected Inspection Notes Action reqd if inspection shows unsatisfactory conditions 1 Monthly i Oil level in SVS ii Connections Check Oil level Check tightnes...

Страница 42: ...heck and replace h One of the phase voltage not getting at input terminal Check each phase voltage 2 Frequent On Off of the output contactor a Auto transformer in any one phase got struck a The mechan...

Страница 43: ...ansformer variac b Clean the commutator surface Of auto transformer variac with clean cotton dipped in petrol and allow it to dry for few seconds c Loose connection at Auto transformer at any point c...

Страница 44: ...ghtness 9 1 Input phase cut off shown in display 2 buzzer continuously ON 3 no movement of Variac Loose connection input output voltage sensing Connector Connect properly 10 1 Display off 2 No movemen...

Страница 45: ...or 020 24390093 09370132704 Manager Service 07507053131 Marketing Manager 09370132710 service technovisionenergy com We Also Manufacture OnlineUPS StaticVoltage Stabilizers Isolation Transformer Batte...

Отзывы: