Program 272 – Solar system with 2 collector panels and charging pump function
Program 272:
Pump
A1
runs, if:
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S3
by the difference
diff1
• and
S3
has not exceeded the threshold
max1
.
Pump
A2
runs, if:
•
S2
exceeds the threshold
min2
• and
S2
is greater than
S3
by the difference
diff1
• and
S3
has not exceeded the threshold
max1
.
The charging pump
A3
runs, if:
•
S5
exceeds the threshold
min3
• and
S5
is greater than
S4
by the difference
diff2
• and
S4
has not exceeded the threshold
max2
.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1
A2 = S2 > (S3 + diff1) & S2 > min2 & S3 < max1
A3 = S5 > (S4 + diff2) & S5 > min3 & S4 < max2
All pr1:
If the difference between the solar panel sensors
S1
and
S2
exceeds the
difference
diff3
the colder panel‘s circuit is deactivated. This prevents heat from being lost
on the colder panel when temperatures are mixed.
All pr2:
Instead of the two pumps
A1
and
A2,
one pump
A1
and a three-way valve
A2
are used. Without priority allocation, collector 2 will be preferred.
WARNING:
This program is not intended for systems with two solar panels fields, since the
usage of a three-way valve always leaves one solar panel field idle.
Note:
The additional application of the priority circuit „All pr1“ is recommended.
necessary settings:
max1
max2
min1
min2
min3
diff1
diff2
diff3
... limit CYL1
S3
... limit CYL2
S4
... activation temp. coll. 1
S1
... activation temp. coll. 2
S2
... activation temp. CYL1
S5
... coll.1
S1
- CYL1
S3
... coll.2
S2
- CYL1
S3
... CYL1
S5
- CYL2
S4
... see all pr1
à
A1, A2
à
A3
à
A1
à
A2
à
A3
à
A1
à
A2
à
A3
Excess temperature limiter 2:
... activate for
S2
and
A2