103
Technician level
Parameters
Adjusting activation, deactivation and difference thresholds
(min/max/diff), Priority ranking (only programs with priorities)
Time program
Setting up 5 time programs with 3 time windows each
Timer
Setting up a timer function
Time/date
Time, date, summer time, automatic time change
Manual mode
Set outputs to
Automatic/Manual ON/Manual OFF
Datalogging Settings
Datalogging to SD card Yes/No, Interval time
Parameter
Chosen
program
(only display)
Value
/
Sensor
(Yes/No = Usage) (Example: Max1 S2)
Off:
Deactivation threshold of the value above (Example: 75.0°C)
On:
Activation threshold (Example: 70.0°C)
Next value
(Example: Max2 / S3)
The hystereses of these values are a result of the difference be
-
tween their activation and deactivation thresholds. As such, a
maximum threshold for example should have its deactivation
threshold should be several degrees above the activation thresh
-
old.
Further down in this menu, you might (depending on the chosen
program) find several maximum thresholds (MAX), minimum
thresholds (MIN) and differential thresholds (DIFF).
Priority ranking
Depending on the chosen program, priority ranking might be
available to be set up for example between two cylinders. The
setting „1-2“ means that element 1 has priority over element 2.
The sort of elements these are and which sensors they corre
-
spond to can be gathered from the chosen program and its dia
-
gram.