Program 352 – Layered cylinder and burner request
Layered system only practical with speed control activated!
(Absolute value control: mode „Normal“ and sensor input S1)
Program 352:
Pumps
A1
run, if:
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S2
by the difference
diff1
• and
S2
has not exceeded the threshold
max1
.
The three-way valve
A2
switches
upwards,
if:
•
S5
exceeds the threshold
min2
•
or,
if
S5
falls below
min2
,
S5
is greater than
S4
by the
difference
diff2
.
• and
S4
has not exceeded the threshold
max2
.
Output
A3
is activated, if
S4
falls below
min3
.
Output
A3
is deactivated (dominantly), if
S3
exceeds the threshold
max3
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2
A3 (on) = S4 < min3 A3 (off) = S3 > max3
All pr1: All pr1:
If
S4
has reached the threshold
max2
, the rapid warm-up
phase is completed and the speed control is blocked, which achieves optimal efficiency.
If control Output A4 is activated, the analogue level for maximum speed will be output. Con
-
trol Output A5 is not affected and continues regulating.
All pr4:
The burner request (
A3
) is only regulated via
S4.
A3 (on) = S4 < min3 A3 (off) = S4 > max3
(dominant)
All pr8:
If the solar circuit is active, the burner request is blocked. If the solar circuit
is inactive, the burner request is unblocked after a 5 minute delay..
necessary settings:
max1
max2
max3
min1
min2
min3
diff1
diff2
... limit CYL
S2
... limit CYL
S4
... burner req. off CYL
S3
... activation temp. coll.
S1
... activation temp. HE
S5
... burner req. on CYL
S4
... coll.
S1
- CYL
S2
... HE
S5
- CYL
S4
à
A1
à
A2
à
A3
à
A1
à
A2
à
A3
à
A1
à
A2