Program 800:
Activation of heating circuit pump
A1,
if sensor
S4
has exceeded the thresh
-
old
min1
. If sensor
S4
is not in use, then the corresponding program setting must be adjust
-
ed accordingly.
All pr1:
Like program 800, but the heating circuit pump
A1
is also enabled via sen
-
sor
S5
and the minimum threshold
min2
(2 generators for the heating circuit).
A1 = ((S4 > min) or (S5 > min2)) & (heating = active)
All pr2:
Like program 800, but the
set flow temperature
is output via control output
A4 (e.g. for burner modulation).
Example: The set flow temperature of 55°C is output via control output A4 as 5,5 Volt. How
-
ever, the voltage being output does not fall below the threshold
min1
. If the pump is deacti
-
vated via a shutdown condition (menu
Shutdown conditions
), then the control output will
output 0,5V. If it is deactivated by the shutdown condition
S4 < min1,
voltage equal to the
set flow temperature (as calculated by the controller) will be output, however not below the
threshold
min1
.
The menu
Technician level/Parameters
features several adjustment settings under the point
Modulation
:
Offset-value
for the set flow temp., range of -50,0K to +50,0K. (FS = 0,0K)
Inverse output
Yes/No, FS = No
Min. output
range of 0.00V - 10.00V, FS = 0.00V
Max. output
range of 0.00V - 10.00V, FS = 10.00V
All pr4:
Like program 800, but the
mixer control
is output via control output A5 (for
mixers with 0-10V-regulation).
The menu
Technician level/Parameters
features adjustment settings under the point
0
-
10V mixer
:
Inverse output
Yes/No, FS = NO
Min. output
range of 0.00V - 10.00V, FS = 0.00V
Max. output
range of 0.00V - 10.00V, FS = 10.00V
Scaling:
0°C = 0.0 V
100°C = 10.0 V