Pasteurisation
Protection against the formation of legionella. If the cylinder temperature does not exceed
the
Temp. threshold
,
measured at the
Monitored sensor
,
for duration of the
Hold time
(if the
Interval time
has passed since this last did occur), an affected output and, if so desired, the
output of a „generator“ (z.g: Burner) is activated for the duration of the
Hold time
and held
above the
Temp. threshold
. If the temp. threshold is exceeded for the duration of the hold
time as per usual automatic operation, the time interval is reset to 0.
No volume flow sensor/encoder:
1
Activate the heat meter profile as in the previous guides.
2
Specify the flow and return sensors in their respective menu
points.
3
Choose „-----“ as flow sensor, since none is in use.
4
Specify the fixed flow rate. Enter the assigned outputs, frost
protection share and calibrate the sensors, as described in the
previous guides.
Enable
Pasteurization function Yes/No (FS = No)
Interval time
Interval in days. If the temperature measured at the monitored
sensor does not exceed the specified temp. threshold within this
time interval for the hold time, the affected outputs will be acti
-
vated.
Monitored sensor
Specifies, which sensor is to be monitored.
Options: S1 to S6 (FS = S3)