108
Expert level
Programming settings
to change basic operation
Sensor menu:
type, designation, correctional values etc.
Ext. sensors
to read sensors and values via CAN-Bus/DL-Bus
Outputs:
Designation, status, meter values, run-on time, blocking
time and blocking protection
Control outputs:
Function, mode etc.
System protection
e.g. Excess temp limiter, frost protection etc.
Start function
to ensure efficiency of solar panel
Solar priority
only visible with a valid program chosen
Funct. check
enable/disable, settings
Heat meter
, Settings for up to 3 heat meter profiles
Pasteurisation
enable/disable, settings
Drainback
only visible with a valid program chosen
CAN/DL-Bus
basic settings
Programming settings
Program
Choice of program according to hydraulic diagram. (FS = 0)
Additional features and functionalities can be added to most pro
-
grams. „All pr1 (+2, +4, +8)“ means, that the chosen program
number must be increased by the sum of the desired additions.
Example:
Program 48 +1 +2 = program number 51 = solar system with
2 consumers, with pump-valve-system and additional sensor S4 for
temperature limitation.
Cancel output
Possibility to exchange the functionalities of outputs with one another
(A1 with A2, A1 with A3 or A2 with A3). This enables the assignment of
the potential free output A3 to wherever necessary (FS = - - - - -)
Assignment of
free outputs
Outputs not used in the program can be assigned to other functional
-
ities.
Off
( = FS)
The unused output remains inactive.
On
The outputs is constantly activated.
And
Linking with one or more outputs. The output is acti
-
vated, if
all
linked outputs are on.
Or
Linking with one or more outputs. The output is acti
-
vated, if
at least one
linked output is on.