Funct. check (Function check)
The function check serves to monitor a system for sensor defects or missing circulation in
a solar system. The function check is deactivated in the factory settings.
Function control
Yes/No
Activate/deactivate (FS = No)
Sensors will be monitored to detect inter
-
ruption and short circuits. Sensors set to
Digital (ON/OFF), VIG or fixed value are
not
monitored.
Circulation check
Yes/No
Circulation check is only useful for monitor
-
ing solar systems. This options enables/
disables the circulation check (FS = No)
Circ. chk 1-3
1-3 is the index of the three available circu
-
lation check options. The numbers set for
each check are the outputs that are to be
monitored for circulation.
Sensor input +
(each circ. check
has its own instance
of this setting)
If the output assigned to the circulation
check is active, the circulation is monitored
according to the following concept:
If the temperature at
sensor input +
exceeds
sensor input -
by 60 K for a dura
-
tion of 30 minutes, a circulation error will
be displayed in the system status.
Sensor input -
(each circ. check
has its own instance
of this setting)
Display on other
devices
This option allows for errors and messages
to be displayed on other CAN-Bus devices.
These can only be viewed on other devices,
not dismissed.
If activated, all errors and messages are
displayed on other devices, not just those
of the function check.