Technical Data
The sensor leads on the inputs with a cross-section of 0.50 mm
2
can be extended to a length
of 50 m.
Consumer (e.g. pumps, valves) with a cable cross-section of 0.75 mm
2
can be connected at
a distance of up to 30 m.
Differential temperature:
adjustable from -100 to +100 K
Minimum / Maximum thresholds:
adjustable from 0 to 200°C
Precision temperature:
typ. 0.4K, max. ±1K in the 0-100°C range
for PT1000 sensors
Precision resistance measurement:
max. 1,6% at 100kΩ (measure: resistance, process vari
-
able: resistance)
Precision voltage:
typ. 1%, max. 3% of the maximum measuring range of the input
Precision outputs 0-10:
max. -2% to +6%
Power supply:
100-230V, 50-60 Hz
Power consumption:
1,5 - 2,0 W, depending on activity of switching outputs
Fuse:
3.15 A fast-acting ( outputs)
Supply cable:
3 x 1mm2 H05VV-F conforming to EN 60730-1 (cable with standard
plug included in the standard sensor pack)
Case (plastic):
ABS, Flame resistance: class V0 conforming to UL94 Norm
Protection rating:
II - safety insulated
Protection class:
IP40
Dimensions (W/H/D):
149.5 / 100 / 56.2 mm
Weight:
with console:
350 g
without console: 234.5 g
Allowed ambient temp.
+5 to +45 °C
6 inputs:
Temperature sensors of types PT1000, KTY (2 kΩ/25°C), Room sen
-
sors RAS or RASPT, Radiation sensor GBS01, Rain sensor RES01,
Digital input
Additionally for input 6:
Impulse input
max. 20 Hz
e.g. for volume flow encoder VIG or wind
sensor WIS01
Output A1:
Relay output, N/O
Output A2:
Relay output, N/O and N/C
Output A3:
Relay changeover contact – potential free
Current load:
Outputs 1-3: max. 2.5 A ohmsch, inductive cos phi 0.6
Control outputs A4 & A5:
Analogue outputs 0-10V (max. 20mA) or PWM (10V/1kHz) in 100
stages each (=0.1V or 1% per stage) or extension option and switch
-
ing output with auxiliary relay modules
max. DL-Bus load
100%
CAN-Bus
Standard data rate 50 kbit/s adjustable from 5 to 500 kbit/s