Program 176 – Solar system with 2 consumers and charging pump functionality
Program 176:
Pump
A1
runs, if:
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S2
by the difference
diff1
• and
S2
has not exceeded the threshold
max1
.
Pump
A2
runs, if:
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S3
by the difference
diff2
• and
S3
has not exceeded the threshold
max2
.
The charging pump
A3
runs, if:
•
S5
exceeds the threshold
min2
• and
S5
is greater than
S4
by the difference
diff3
• and
S4
has not exceeded the threshold
max3
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2
A3 = S5 > (S4 + diff3) & S5 > min2 & S4 < max3
All pr1:
Instead of the two pumps
A1
and
A2,
one pump
A1
and a three-way valve
A2
are used.
Without priority allocation, cylinder 2 is filled by default.
All pr2:
If both cylinders have reached their maximum temperatures due to the so
-
lar system, pump
A3
is activated (re-cooling function).
All pr4:
Both solar circuits have separate activation thresholds at
S1:
Output
A1
retains
min1
, and
A2
is regulated via
min3
.
necessary settings:
max1
max2
max3
min1
min2
min3
diff1
diff2
diff3
... limit CYL1
S2
... limit CYL2
S3
... limit CYL1
S4
... activation temp. coll.
S1
... activation temp. CYL2
S5
... see all pr4
... coll.
S1
- CYL1
S2
... coll.
S1
- CYL2
S3
... SP2
S5
- CYL1
S4
à
A1
à
A2
à
A3
à
A1, A2
à
A3
à
A1
à
A2
à
A3
Excess temperature limiter:
... activate for
S1
and
A1+A2
A1
... mutual pump
A2
... valve (A2/NO receives voltage when filling CYL2)