159
Output mode, Correcting variables
Depending on the make of the pump, the control mode of the pump
can be set to normal (0-100 „solar mode“, PWM 2) or inverse (100-
0 „heating mode“, PWM 1). There may also be specific require
-
ments for the limits of the control range. These can be found in the
information of the pump manufacturer.
The following parameters define the control mode and the lower
and upper limits of the output analogue value:
Output mode:
0-100 equals 0-10V and 0-100% PWM, 100-0 equals
10-0V and 100-0% PWM (inverse). (FS = 0-100)
Min. correcting variable:
Lower speed limit (FS = 0)
Max. correcting variable:
Upper speed limit (FS = 100)
Control delay, control commands
Control delay:
If the control output is activated by an assigned out
-
put, the speed control will be deactivated for this set time and the
variable for maximum speed will be output. Only after this time
elapsed, the control output will be regulated. (FS = 0)
Min. switch-off time:
The control output can only be activated if the
minimum switch-off time has elapsed since its last activation.
(FS = 0)
Current correcting var.:
Current correcting variable used for regu
-
lation.
Test correcting var:
For testing purposes, a specific correcting vari
-
able can be output. Entering this menu automatically sets the con
-
trol output into manual mode. Leaving the menu sets it back to
regular automatic regulation.