Installation of the electrolytic capacitor
In order to reduce the phenomenon of temperature spikes read from the zone sensor, a 220uF/25V low impedance
electrolytic capacitor, connected in parallel with the sensor cable, should be installed. When installing the capacitor,
always pay particular attention to its polarity. The ground of the element marked with a white strip is screwed into the
right terminal of the sensor connector, as seen from the front of the controller, and depicted in attached images. The
second terminal of the capacitor is screwed into the terminal of the left connector. We found that this solution has
completely eliminated potential distortions. However, it is worth noting that the basic principle is to correctly install the
wires in order to avoid interference. The wiring should not be routed near sources of electromagnetic field, however, if
such a situation has already occurred, a filter in the form of a capacitor should be applied.