3.
CONTROLLER SETTINGS
➢
Time settings -
the current time and date can be automatically downloaded from the network if the Internet
module is connected and the automatic mode is enabled. It is also possible for the user to manually set the time
and date if the automatic mode does not operate correctly.
➢
Screen settings -
This function allows the user to customize the display.
➢
Sound the buttons -
this option is used to enable the sound that will accompany pressing the buttons.
4.
FITTER’S
MENU
The
fitter’s
menu is the most complex controller menu. Here, the user has a wide selection of functions that allow for
maximum use of the controller's capabilities.
4.1.
ZONES
To activate a zone on the controller display, register/activate a sensor therein and then activate the zone.
4.1.1.
ROOM SENSOR
T
he user can register/enable any type of sensor: NTC wired, RS or wireless.
➢
Hysteresis
-
adds a tolerance for the room temperature in the range of 0.1 ÷ 5°C, at which there is additional
heating/cooling enabled.
Example:
The preset room temperature is 23°C
Hysteresis is 1°C
The room sensor will start to indicate room underheating after t
he temperature drops to 22°C.
➢
Calibration
- Room sensor calibration is carried out during assembly or after a longer period of use of the sensor if
the displayed room temperature deviates from the actual one. Adjustment range: from -
10°C to +10°C with a s
tep
of 0.1°C.
4.1.2.
SET TEMPERATURE
The function is described in the
Menu → Zones
section.
4.1.3.
OPERATION MODE
The function is described in the
Menu → Zones
section.
4.1.4.
OUTPUTS CONFIGURATION
This option controls the outputs: floor pump, no-voltage contact and outputs of sensors 1-8 (NTC to control the temperature
in the zone or floor sensor to control the temperature of the floor). Sensor outputs 1-8 are assigned to zones 1-8, respectively.
The type of sensor selected here will appear by default in the option:
Menu →
Fi
tter’s
menu →
Zones → Zones... →
Room
sensor → Select sensor
(for temperature sensor) and
Menu → Fitter’s
Menu
→ Zones → Zones… → Floor heating → Floor
sensor → Select sensor
(for floor sensor).
The outputs of both sensors are used to register the zone by wire.
The function also allows switching off the pump and the contact in a given zone. Such a zone, despite the need for heating,
will not participate in the control.