4.1.7.
WINDOW SENSORS
➢
Settings
•
On
- the function enables the activation of window sensors in a given zone (window sensor registration
required).
•
Delay Time
- This function allows you to set the delay time. After the preset delay time, the main controller
responds to the opening of the window and blocks heating or cooling in the respective zone.
Example: The delay time is set to 10 minutes. Once the window is opened, the sensor sends information to the main
controller about opening the window. The sensor confirms the current state of the window from time to time. If
after the delay time (10 minutes) the window remains open, the main controller will close the actuators and turn off
the overheating of the zone.
CAUTION
If the delay time is set to 0, then the signal to the actuators to close will be transmitted immediately.
➢
Wireless
–
option to register window sensors (1-6 pcs per zone). To do this, select
Register
and briefly press the
communication button on the sensor. After successful registration, an additional
Information
function appears,
where the user can view the sensor parameters, e.g. battery status, range, etc. It is also possible to delete a given
sensor or all at the same time.
4.1.8.
FLOOR HEATING
➢
Floor Sensor
•
Sensor Selection
- This function is used to enable (wired) or register (wireless) floor sensors. In the case of a
wireless sensor, register it by additionally pressing the communication button on the sensor.
•
Hysteresis
-
adds a tolerance for the room temperature in the range of 0.1 ÷ 5°C, at which the
additional
heating/cooling is enabled.
Example:
The maximum floor temperature is 45°C
Hysteresis is 2°C
The controller will deactivate the contact after exceeding 45°C at the floor sensor. If the temperature starts to drop,
the contact will be switched back on again after the temperature at the floor sensor drops to 43 C (unless the room
temperature has been reached).
•
Calibration
- Floor sensor calibration is carried out during assembly or after a longer period of use of the sensor
if the displayed floor temperature deviates from the actual one. Adjustment range: from -
10°C to +10°C with a
step of 0.1°C.
CAUTION
The floor sensor is not used during the cooling mode.