Tech Controllers EU-L-X WiFi Скачать руководство пользователя страница 21

 

Heating curve

 - this is the curve according to which the set temperature of the controller is determined 

on the basis of the external temperature. In order for the valve to operate properly, the set temperature 
(downstream the valve) is set for four intermediate external temperatures: -

20°C, 

-

10°C, 0°C and 10°C.

 

There is a separate heating curve for the 

Cooling

 mode. It is set for intermediate outdoor temperatures 

of: 10°C,

 

20°C, 30°C, 40°C.

 

 

 

Room regulator  

 

Controller type 

 

Control without room regulator

 -

 

This option should be checked when we do not want the room regulator to affect 

the operation of the valve.

 

 

RS  regulator  -  decrease

  -

 

check  this  option  if  the  valve  is  to  be  controlled  by  a  room  regulator  equipped  with  RS 

communication.  When  this  function  is  checked,  the  controller  will  operate  according  to  the 

Lower  room  temp.

 

parameter. 

 

RS regulator  - proportion

 -

 

When this  regulator is switched on, the current  boiler and valve temperatures can be 

viewed. With this function checked, the controller will operate according to the 

Room Temperature Difference

 

and 

Setpoint Temperature Change

 parameters. 

 

Standard room regulator 

- this option is checked if the valve is to be controlled by a two-state regulator (not equipped 

with RS communication). When this function is checked, the controller will operate according to the 

Room regulator 

temperature lower

 parameter. 

 

 

Room regulator temp. lower 

-

 

In this setting, set the value by which the valve will lower its set temperature 

once the temperature set in the room regulator is reached (room heating). 

 
CAUTION  

This parameter applies to the 

Standard room regulator

 

and 

RS regulator decrease

 functions. 

 

 

Room temperature difference

 -

 

This setting determines the unit change in the current room temperature 

(to the nearest 0.1°C) at which a specific change in the set temperature of the valve will occur.

 

 

 

Change of the set temperature 

- This setting determines how many degrees the valve temperature will 

increase or decrease with a unit change in room temperature (see: 

Room temperature difference

). This 

function is only active with the RS room regulator and is closely related to the 

Room temperature difference

 

parameter. 

 

Example: Room temperature difference: 0.5°C

 

Valve set temperature change: 

1°C

 

Valve set temperature: 40°C

 

Room regulator 

set temperature: 23°C

 

If the room temperature rises to 23.5°C (by 0.5°C above the set room 

temperature), the valve closes to the 

39°C preset (by 1°C).

 

 
CAUTION 

The parameter applies to the 

RS proportional regulator

 function. 

 

 

Room regulator function 

- In this function, it is necessary to set whether the valve will close (

Closing

) or 

the temperature will lower (

Room regulator temperature lower

) once it is heated. 

 

Содержание EU-L-X WiFi

Страница 1: ...EU L X WiFi...

Страница 2: ...4 5 Manual mode 25 4 6 External sensor 25 4 7 heating stopping 25 4 8 Potential free contact 26 4 9 Pump 26 4 10 Heating cooling 26 4 11 Anti stop settings 26 4 12 Maximum humidity 26 4 13 Language 2...

Страница 3: ...The regulator should not be operated by children WARNING The device may be damaged if struck by a lightning Make sure the plug is disconnected from the power supply during storm Any use other than spe...

Страница 4: ...number of functions support for EU R 12b EU R 12s and EU F 12b cable regulators support for floor temperature sensors support for external sensors and weather controls support for wireless window sens...

Страница 5: ......

Страница 6: ...connections Before working on the controller disconnect its power supply and secure it against accidental switching on CAUTION Incorrect wiring may damage the controller An illustrative diagram showi...

Страница 7: ...d into the right terminal of the sensor connector as seen from the front of the controller and depicted in attached images The second terminal of the capacitor is screwed into the terminal of the left...

Страница 8: ...r in the ON position in the controller and the last of the regulators When connecting regulators to a controller located in the middle of the transmission line terminate switch the jumper to the ON po...

Страница 9: ...ime can be adjusted from the network automatically Step 4 Configure temperature sensors room regulators In order for the EU L X WiFi controller to support a given zone it must receive information abou...

Страница 10: ...s the operation parameters between the zones 3 button used to browse the menu functions or increase the value of the edited parameters This button also switches the operation parameters between the zo...

Страница 11: ...cooling depending on the mode the digit flashes If an alarm occurs in a given zone an exclamation mark will be displayed instead of a digit To view the current operating parameters of a specific zone...

Страница 12: ...ature The set temperature in the zone results from the settings of a specific mode of operation in the zone i e the weekly schedule However it is possible to turn off the schedule and set a separate t...

Страница 13: ...ing the MENU button Use the MENU button to go to the settings of the time intervals and the set temperature that will be valid for the specified time interval set it using the arrows confirm with the...

Страница 14: ...steresis is 1 C The room sensor will start to indicate room underheating after the temperature drops to 22 C Calibration Room sensor calibration is carried out during assembly or after a longer period...

Страница 15: ...s information to automatically activate the heating in advance of the time required to reach the set temperatures This system does not require any involvement on the part of the user and precisely res...

Страница 16: ...n the zone temperature reaches the set point Once the set point is reached the temperature in the zone will start to drop When it reaches 21 C set temperature minus hysteresis value the actuator will...

Страница 17: ...tration an additional Information function appears where the user can view the sensor parameters e g battery status range etc It is also possible to delete a given sensor or all at the same time 4 1 8...

Страница 18: ...llation from overheating 4 2 ADDITIONAL CONTACTS The function allows you to handle additional contacts First of all it is necessary to register such a contact 1 6 pcs To do this select the Registratio...

Страница 19: ...e Calibration This function can be used to calibrate the built in valve e g after prolonged use During calibration the valve is set to a safe position i e for the CH valve and the Return protection ty...

Страница 20: ...y in a short circuit while the full opening of the valve 100 means that the short circuit is closed and the water flows through the entire central heating system CAUTION If the Boiler Protection is of...

Страница 21: ...When this function is checked the controller will operate according to the Room regulator temperature lower parameter Room regulator temp lower In this setting set the value by which the valve will l...

Страница 22: ...take into account the Self of the valve module or the Main sensor Only in slave mode Boiler protection This provides protection against excessive CH temperature and is intended to prevent dangerous i...

Страница 23: ...e deviations set are in the range of 10 C To enable weekly control select and check Mode 1 or Mode 2 Detailed settings of these modes can be found in the following sections of the submenu Set Mode 1 a...

Страница 24: ...on The user can control the operation of various devices and change some parameters using the emodul pl application The device has a built in Internet module After switching on the Internet module and...

Страница 25: ...to 10 C with a step of 0 1 C In the case of a wireless sensor the subsequent parameters relate to the range and level of the battery 4 7 HEATING STOPPING Function to prevent actuators from turning on...

Страница 26: ...operating mode Heating all zones are heated Cooling all zones are cooled Automatic the controller switches the mode between heating and cooling based on the two state input 4 11 ANTI STOP SETTINGS Thi...

Страница 27: ...sensor Replace the sensor with a new one or contact the service staff if necessary No communication with sensor wireless regulator No range No battery Flat battery Put the sensor regulator in a differ...

Страница 28: ...the controller has been installed properly Replace the batteries Calibrate actuator again by holding the communication button until the third flash of green light Call the service staff ERROR 3 Calib...

Страница 29: ...arried out by a qualified installer After changing the software it is not possible to restore the previous settings Do not turn off the controller while updating the software IX TECHNICAL DATA AC1 loa...

Страница 30: ...equipment implementing provisions of Directive EU 2017 2102 of the European Parliament and of the Council of 15 November 2017 amending Directive 2011 65 EU on the restriction of the use of certain ha...

Страница 31: ......

Страница 32: ......

Отзывы: