Tech Controllers EU-L-X WiFi Скачать руководство пользователя страница 24

 

 

MODE 2

 - in this mode, it is possible to program the temperature deviations in detail for all 

working days

 (Monday 

 

Friday) and for the 

weekend

 (Saturday 

 Sunday). To do this: 

 

Select the option: 

Set Mode 2

 

 

Select the part of the week for which you wish to change the temperature settings 

 

The further procedure is the same as in 

Mode 1

 

 

Example:

 

 

 

 
 
 
 
 
 
 
 

In  this  case,  if  the  temperature  set  on  the  valve  is  50°C  Monday  to  Friday,  from  4

00

 

 

to  7

00

,  the  temperature  on  the  valve  will  increase  by  5°C,  or  to  55°C;  in  the  hours  from  7

00

  to  14

00

  it  will

 

 decrease by 10°C, so it will be 40°C, while between 17

00

 and 22

00

 it will increase to 57°C.

 

During the weekend, from 6

00

 to 9

00

 hours, the temperature on the valve will rise by 5°C, that is to 55°C, and between 

17

00 

and 22

00 

it will rise to 57°C.

 

 

 

Factory settings 

 This parameter allows you to return to the settings of a given valve saved by the manufacturer. 

Restoring the factory settings changes the valve type to a CH valve. 

4.4.

 

INTERNET MODULE 

 
The Internet module is a device that allows remote control of the installation. The user can control the operation of various 
devices and change some parameters using the 

emodul.pl

 

application. 

 
The  device  has  a  built-in  Internet  module.  After  switching  on  the  Internet  module  and  selecting  the  DHCP  option,  the 
controller will automatically retrieve parameters such as: IP address, IP mask, Gateway address and DNS address from the 
local network.  
 

Required network settings 

In order for the Internet module to operate correctly, it is required to connect the module to a network with a DHCP 

server and an open port 2000. Once the Internet module is properly connected to the network, go to the module settings 
menu (in the master controller). If the network does not have a DHCP server, the Internet module must be configured by its 
administrator by entering the appropriate parameters (DHCP,  IP Address, Gateway Address, Subnet Mask, DNS Address). 
Configuration can be accomplished by:  

1.

 

Go to the settings menu of the Internet module. 

2.

 

Select the "Enabled" option 

3.

 

Then check if the "DHCP" option is checked. 

4.

 

Enter “WIFI Selection”

 

5.

 

Then select your WIFI network and enter its password. 

 

Time 

Temperature

 - Set for 

weekly control

 

Monday - Friday

 

PRESET

 

4

00 

‐ 7

00

 

+5°C

 

7

00 

‐ 14

00

 

‐10°C

 

17

00 

‐ 22

00

 

+7°C

 

Saturday - Sunday

 

PRESET

 

6

00 

‐ 9

00

 

+5°C

 

17

00 

‐ 22

00

 

+7°C

 

Содержание EU-L-X WiFi

Страница 1: ...EU L X WiFi...

Страница 2: ...4 5 Manual mode 25 4 6 External sensor 25 4 7 heating stopping 25 4 8 Potential free contact 26 4 9 Pump 26 4 10 Heating cooling 26 4 11 Anti stop settings 26 4 12 Maximum humidity 26 4 13 Language 2...

Страница 3: ...The regulator should not be operated by children WARNING The device may be damaged if struck by a lightning Make sure the plug is disconnected from the power supply during storm Any use other than spe...

Страница 4: ...number of functions support for EU R 12b EU R 12s and EU F 12b cable regulators support for floor temperature sensors support for external sensors and weather controls support for wireless window sens...

Страница 5: ......

Страница 6: ...connections Before working on the controller disconnect its power supply and secure it against accidental switching on CAUTION Incorrect wiring may damage the controller An illustrative diagram showi...

Страница 7: ...d into the right terminal of the sensor connector as seen from the front of the controller and depicted in attached images The second terminal of the capacitor is screwed into the terminal of the left...

Страница 8: ...r in the ON position in the controller and the last of the regulators When connecting regulators to a controller located in the middle of the transmission line terminate switch the jumper to the ON po...

Страница 9: ...ime can be adjusted from the network automatically Step 4 Configure temperature sensors room regulators In order for the EU L X WiFi controller to support a given zone it must receive information abou...

Страница 10: ...s the operation parameters between the zones 3 button used to browse the menu functions or increase the value of the edited parameters This button also switches the operation parameters between the zo...

Страница 11: ...cooling depending on the mode the digit flashes If an alarm occurs in a given zone an exclamation mark will be displayed instead of a digit To view the current operating parameters of a specific zone...

Страница 12: ...ature The set temperature in the zone results from the settings of a specific mode of operation in the zone i e the weekly schedule However it is possible to turn off the schedule and set a separate t...

Страница 13: ...ing the MENU button Use the MENU button to go to the settings of the time intervals and the set temperature that will be valid for the specified time interval set it using the arrows confirm with the...

Страница 14: ...steresis is 1 C The room sensor will start to indicate room underheating after the temperature drops to 22 C Calibration Room sensor calibration is carried out during assembly or after a longer period...

Страница 15: ...s information to automatically activate the heating in advance of the time required to reach the set temperatures This system does not require any involvement on the part of the user and precisely res...

Страница 16: ...n the zone temperature reaches the set point Once the set point is reached the temperature in the zone will start to drop When it reaches 21 C set temperature minus hysteresis value the actuator will...

Страница 17: ...tration an additional Information function appears where the user can view the sensor parameters e g battery status range etc It is also possible to delete a given sensor or all at the same time 4 1 8...

Страница 18: ...llation from overheating 4 2 ADDITIONAL CONTACTS The function allows you to handle additional contacts First of all it is necessary to register such a contact 1 6 pcs To do this select the Registratio...

Страница 19: ...e Calibration This function can be used to calibrate the built in valve e g after prolonged use During calibration the valve is set to a safe position i e for the CH valve and the Return protection ty...

Страница 20: ...y in a short circuit while the full opening of the valve 100 means that the short circuit is closed and the water flows through the entire central heating system CAUTION If the Boiler Protection is of...

Страница 21: ...When this function is checked the controller will operate according to the Room regulator temperature lower parameter Room regulator temp lower In this setting set the value by which the valve will l...

Страница 22: ...take into account the Self of the valve module or the Main sensor Only in slave mode Boiler protection This provides protection against excessive CH temperature and is intended to prevent dangerous i...

Страница 23: ...e deviations set are in the range of 10 C To enable weekly control select and check Mode 1 or Mode 2 Detailed settings of these modes can be found in the following sections of the submenu Set Mode 1 a...

Страница 24: ...on The user can control the operation of various devices and change some parameters using the emodul pl application The device has a built in Internet module After switching on the Internet module and...

Страница 25: ...to 10 C with a step of 0 1 C In the case of a wireless sensor the subsequent parameters relate to the range and level of the battery 4 7 HEATING STOPPING Function to prevent actuators from turning on...

Страница 26: ...operating mode Heating all zones are heated Cooling all zones are cooled Automatic the controller switches the mode between heating and cooling based on the two state input 4 11 ANTI STOP SETTINGS Thi...

Страница 27: ...sensor Replace the sensor with a new one or contact the service staff if necessary No communication with sensor wireless regulator No range No battery Flat battery Put the sensor regulator in a differ...

Страница 28: ...the controller has been installed properly Replace the batteries Calibrate actuator again by holding the communication button until the third flash of green light Call the service staff ERROR 3 Calib...

Страница 29: ...arried out by a qualified installer After changing the software it is not possible to restore the previous settings Do not turn off the controller while updating the software IX TECHNICAL DATA AC1 loa...

Страница 30: ...equipment implementing provisions of Directive EU 2017 2102 of the European Parliament and of the Council of 15 November 2017 amending Directive 2011 65 EU on the restriction of the use of certain ha...

Страница 31: ......

Страница 32: ......

Отзывы: