Tech Controllers EU-L-X WiFi Скачать руководство пользователя страница 23

 

 

Pump anti-stop

 - When enabled, the valve pump will turn on every 10 days for 2 minutes. This prevents water 

from fouling the installation outside the heating season. 

 

Closing below temperature threshold

 - When this function is activated (check the Enabled option), the valve 

will remain closed until the boiler sensor reaches the pump switching temperature. 

CAUTION 

If the additional valve module is an i-1 model, the anti-fouling functions of the pumps and the closure 
below the threshold can be set directly from the sub-menu of that module. 

 

 

Valve pump room regulator

 - Option whereby the room regulator switches the pump off once heated. 

 

Only pump

 - When enabled, the controller controls only the pump and the valve is not controlled. 

 

 

External sensor calibration 

 This function is used to adjust the external sensor, it is done during installation or after 

prolonged use of the sensor if the displayed external temperature deviates from the actual one. The user specifies 

the correction value applied (adjustment range: ‐10 to +10°C).

 

 

 

Valve closing

 

 Parameter in which the behaviour of the valve in the CH mode is set after it is switched off. Enabling 

this option closes the valve and disabling opens it. 
 

 

Valve  weekly  control

 

 

The  weekly  control  allows  you  to  program  deviations  of  the  valve  set  temperature  on 

particular days of the week at specific times. The temperature deviations set are in the range of +/-

10°C.

 

 
To enable weekly control, select and check 

Mode 1

 

or 

Mode 2

. Detailed settings of these modes can be found in the 

following sections of the submenu: 

Set Mode 1

 

and 

Set Mode 2

 

PLEASE NOTE 

For the correct operation of this function, it is necessary to set the current date and time. 

MODE 1

 - in this mode it is possible to program deviations of the set temperature for 

each day of the week 

separately

. To do this: 

 

Select the option: 

Set Mode 1

 

 

Select the day of the week for which you wish to change the temperature settings 

 

Use the 

 buttons to select the time for which you want to change the temperature. Confirm the 

selection by pressing the MENU button 

 

Options appear at the bottom, select CHANGE by pressing the MENU button when it is  highlighted in 
white. 

 

Then decrease or increase the temperature by the selected value and confirm. 

 

If you want to apply the same change also to the neighboring hours, press the MENU button on the 
selected setting, and after the option appears at the bottom of the screen, select COPY and copy the 
setting to the subsequent or previous hour using the 

 buttons. Confirm the settings by pressing 

MENU. 

Example: 

 

In 

this 

case, 

if 

the 

temperature 

set 

on 

the 

valve 

is 

50°C, 

on 

Mondays, 

from 

4

00

 

 

to 7

00

 hours, the temperature set on the valve will increase by 5°C, or to 55°C; in the hours from 7

00

 to 14

00

 it will decrease 

by 10°C, so it will be 40°C, while between 17

00

 and 22

00

 it will increase to 57°C.

 

 

Time 

Temperature

 

 Set for  

weekly control

 

Monday

 

PRESET

 

4

00 

‐ 7

00

 

+5°C

 

7

00 

‐ 14

00

 

‐10°C

 

17

00 

‐ 22

00

 

+7°C

 

Содержание EU-L-X WiFi

Страница 1: ...EU L X WiFi...

Страница 2: ...4 5 Manual mode 25 4 6 External sensor 25 4 7 heating stopping 25 4 8 Potential free contact 26 4 9 Pump 26 4 10 Heating cooling 26 4 11 Anti stop settings 26 4 12 Maximum humidity 26 4 13 Language 2...

Страница 3: ...The regulator should not be operated by children WARNING The device may be damaged if struck by a lightning Make sure the plug is disconnected from the power supply during storm Any use other than spe...

Страница 4: ...number of functions support for EU R 12b EU R 12s and EU F 12b cable regulators support for floor temperature sensors support for external sensors and weather controls support for wireless window sens...

Страница 5: ......

Страница 6: ...connections Before working on the controller disconnect its power supply and secure it against accidental switching on CAUTION Incorrect wiring may damage the controller An illustrative diagram showi...

Страница 7: ...d into the right terminal of the sensor connector as seen from the front of the controller and depicted in attached images The second terminal of the capacitor is screwed into the terminal of the left...

Страница 8: ...r in the ON position in the controller and the last of the regulators When connecting regulators to a controller located in the middle of the transmission line terminate switch the jumper to the ON po...

Страница 9: ...ime can be adjusted from the network automatically Step 4 Configure temperature sensors room regulators In order for the EU L X WiFi controller to support a given zone it must receive information abou...

Страница 10: ...s the operation parameters between the zones 3 button used to browse the menu functions or increase the value of the edited parameters This button also switches the operation parameters between the zo...

Страница 11: ...cooling depending on the mode the digit flashes If an alarm occurs in a given zone an exclamation mark will be displayed instead of a digit To view the current operating parameters of a specific zone...

Страница 12: ...ature The set temperature in the zone results from the settings of a specific mode of operation in the zone i e the weekly schedule However it is possible to turn off the schedule and set a separate t...

Страница 13: ...ing the MENU button Use the MENU button to go to the settings of the time intervals and the set temperature that will be valid for the specified time interval set it using the arrows confirm with the...

Страница 14: ...steresis is 1 C The room sensor will start to indicate room underheating after the temperature drops to 22 C Calibration Room sensor calibration is carried out during assembly or after a longer period...

Страница 15: ...s information to automatically activate the heating in advance of the time required to reach the set temperatures This system does not require any involvement on the part of the user and precisely res...

Страница 16: ...n the zone temperature reaches the set point Once the set point is reached the temperature in the zone will start to drop When it reaches 21 C set temperature minus hysteresis value the actuator will...

Страница 17: ...tration an additional Information function appears where the user can view the sensor parameters e g battery status range etc It is also possible to delete a given sensor or all at the same time 4 1 8...

Страница 18: ...llation from overheating 4 2 ADDITIONAL CONTACTS The function allows you to handle additional contacts First of all it is necessary to register such a contact 1 6 pcs To do this select the Registratio...

Страница 19: ...e Calibration This function can be used to calibrate the built in valve e g after prolonged use During calibration the valve is set to a safe position i e for the CH valve and the Return protection ty...

Страница 20: ...y in a short circuit while the full opening of the valve 100 means that the short circuit is closed and the water flows through the entire central heating system CAUTION If the Boiler Protection is of...

Страница 21: ...When this function is checked the controller will operate according to the Room regulator temperature lower parameter Room regulator temp lower In this setting set the value by which the valve will l...

Страница 22: ...take into account the Self of the valve module or the Main sensor Only in slave mode Boiler protection This provides protection against excessive CH temperature and is intended to prevent dangerous i...

Страница 23: ...e deviations set are in the range of 10 C To enable weekly control select and check Mode 1 or Mode 2 Detailed settings of these modes can be found in the following sections of the submenu Set Mode 1 a...

Страница 24: ...on The user can control the operation of various devices and change some parameters using the emodul pl application The device has a built in Internet module After switching on the Internet module and...

Страница 25: ...to 10 C with a step of 0 1 C In the case of a wireless sensor the subsequent parameters relate to the range and level of the battery 4 7 HEATING STOPPING Function to prevent actuators from turning on...

Страница 26: ...operating mode Heating all zones are heated Cooling all zones are cooled Automatic the controller switches the mode between heating and cooling based on the two state input 4 11 ANTI STOP SETTINGS Thi...

Страница 27: ...sensor Replace the sensor with a new one or contact the service staff if necessary No communication with sensor wireless regulator No range No battery Flat battery Put the sensor regulator in a differ...

Страница 28: ...the controller has been installed properly Replace the batteries Calibrate actuator again by holding the communication button until the third flash of green light Call the service staff ERROR 3 Calib...

Страница 29: ...arried out by a qualified installer After changing the software it is not possible to restore the previous settings Do not turn off the controller while updating the software IX TECHNICAL DATA AC1 loa...

Страница 30: ...equipment implementing provisions of Directive EU 2017 2102 of the European Parliament and of the Council of 15 November 2017 amending Directive 2011 65 EU on the restriction of the use of certain ha...

Страница 31: ......

Страница 32: ......

Отзывы: