Pump anti-stop
- When enabled, the valve pump will turn on every 10 days for 2 minutes. This prevents water
from fouling the installation outside the heating season.
•
Closing below temperature threshold
- When this function is activated (check the Enabled option), the valve
will remain closed until the boiler sensor reaches the pump switching temperature.
CAUTION
If the additional valve module is an i-1 model, the anti-fouling functions of the pumps and the closure
below the threshold can be set directly from the sub-menu of that module.
•
Valve pump room regulator
- Option whereby the room regulator switches the pump off once heated.
•
Only pump
- When enabled, the controller controls only the pump and the valve is not controlled.
➢
External sensor calibration
–
This function is used to adjust the external sensor, it is done during installation or after
prolonged use of the sensor if the displayed external temperature deviates from the actual one. The user specifies
the correction value applied (adjustment range: ‐10 to +10°C).
➢
Valve closing
–
Parameter in which the behaviour of the valve in the CH mode is set after it is switched off. Enabling
this option closes the valve and disabling opens it.
➢
Valve weekly control
–
The weekly control allows you to program deviations of the valve set temperature on
particular days of the week at specific times. The temperature deviations set are in the range of +/-
10°C.
To enable weekly control, select and check
Mode 1
or
Mode 2
. Detailed settings of these modes can be found in the
following sections of the submenu:
Set Mode 1
and
Set Mode 2
.
PLEASE NOTE
For the correct operation of this function, it is necessary to set the current date and time.
MODE 1
- in this mode it is possible to program deviations of the set temperature for
each day of the week
separately
. To do this:
→
Select the option:
Set Mode 1
→
Select the day of the week for which you wish to change the temperature settings
→
Use the
buttons to select the time for which you want to change the temperature. Confirm the
selection by pressing the MENU button
→
Options appear at the bottom, select CHANGE by pressing the MENU button when it is highlighted in
white.
→
Then decrease or increase the temperature by the selected value and confirm.
→
If you want to apply the same change also to the neighboring hours, press the MENU button on the
selected setting, and after the option appears at the bottom of the screen, select COPY and copy the
setting to the subsequent or previous hour using the
buttons. Confirm the settings by pressing
MENU.
Example:
In
this
case,
if
the
temperature
set
on
the
valve
is
50°C,
on
Mondays,
from
4
00
to 7
00
hours, the temperature set on the valve will increase by 5°C, or to 55°C; in the hours from 7
00
to 14
00
it will decrease
by 10°C, so it will be 40°C, while between 17
00
and 22
00
it will increase to 57°C.
Time
Temperature
–
Set for
weekly control
Monday
PRESET
4
00
‐ 7
00
+5°C
7
00
‐ 14
00
‐10°C
17
00
‐ 22
00
+7°C