Operation mode 

 

 

Off

 

 Selecting this option disables the floor heating mode, i.e. 

Floor Protection

 

nor 

Comfort Mode

 are not active. 

 

 

Floor protection

 

 This function is used to keep the floor temperature below the set maximum temperature to 

protect the system from overheating. When the temperature rises to the set maximum temperature, the reheating 
of the zone will be switched off. 
 

 

Comfort mode

 

 This function is used to maintain a comfortable floor temperature, i.e. the controller will monitor 

the current temperature. When the temperature rises to the set maximum temperature, the zone heating will be 
switched off to protect the system from overheating. When the floor temperature drops below the set minimum 
temperature, the zone reheat will be switched back on. 

 

 

Min. temperature 

The  function  is  used  to  set  the  minimum  temperature  to  protect  the  floor  from  cooling  down.  When  the  floor 
temperature drops below the set minimum temperature, the zone reheat will be switched back on. This function is only 
available when you select 

Comfort Mode

 

Max. temperature 

The  maximum  floor  temperature  is  the  floor  temperature  threshold  above  which  the  controller  will  switch  off  the 
heating regardless of the current room temperature. This function protects the installation from overheating. 

4.2.

 

ADDITIONAL CONTACTS 

The function allows you to handle additional contacts. First of all, it is necessary to register such a contact (1-6 pcs.). To do 
this, select the 

Registration

 option and briefly press the communication button on the device, e.g. MW-1.  

After registering and switching on the device, the following functions will appear: 

 

Information

 - information about the status, operating mode and contact range is displayed on the controller screen  

 

On

 - option to enable/disable contact operation

 

 

Operating mode 

 user available option to activate the selected contact operation mode

 

 

Time mode 

 the function allows setting the contact operation time for a specific time 

The user can change the contact status by selecting/deselecting the 

Active

 option

 and then setting 

the 

Duration

 

of 

this mode 

 

Constant mode 

 the function allows setting the contact to operate permanently. It is possible to change the contact 

status by selecting/deselecting the 

Active

 option 

 

Relays 

 

the contact works according to the zones to which it has been assigned 

 

Dehumidification 

 if the 

Maximum Humidity is exceeded in a given zone,

 this

 

option allows you to start the air 

dryer 

 

Schedule settings 

 the function allows you to set a separate contact operation schedule (regardless of the status 

of the controller zones).  

CAUTION 

The 

Dehumidification 

function works only in the 

Cooling

 operation mode. 

 

Delete

 

 

this option is used to delete the selected contact. 

 

 

Содержание EU-L-X WiFi

Страница 1: ...EU L X WiFi...

Страница 2: ...4 5 Manual mode 25 4 6 External sensor 25 4 7 heating stopping 25 4 8 Potential free contact 26 4 9 Pump 26 4 10 Heating cooling 26 4 11 Anti stop settings 26 4 12 Maximum humidity 26 4 13 Language 2...

Страница 3: ...The regulator should not be operated by children WARNING The device may be damaged if struck by a lightning Make sure the plug is disconnected from the power supply during storm Any use other than spe...

Страница 4: ...number of functions support for EU R 12b EU R 12s and EU F 12b cable regulators support for floor temperature sensors support for external sensors and weather controls support for wireless window sens...

Страница 5: ......

Страница 6: ...connections Before working on the controller disconnect its power supply and secure it against accidental switching on CAUTION Incorrect wiring may damage the controller An illustrative diagram showi...

Страница 7: ...d into the right terminal of the sensor connector as seen from the front of the controller and depicted in attached images The second terminal of the capacitor is screwed into the terminal of the left...

Страница 8: ...r in the ON position in the controller and the last of the regulators When connecting regulators to a controller located in the middle of the transmission line terminate switch the jumper to the ON po...

Страница 9: ...ime can be adjusted from the network automatically Step 4 Configure temperature sensors room regulators In order for the EU L X WiFi controller to support a given zone it must receive information abou...

Страница 10: ...s the operation parameters between the zones 3 button used to browse the menu functions or increase the value of the edited parameters This button also switches the operation parameters between the zo...

Страница 11: ...cooling depending on the mode the digit flashes If an alarm occurs in a given zone an exclamation mark will be displayed instead of a digit To view the current operating parameters of a specific zone...

Страница 12: ...ature The set temperature in the zone results from the settings of a specific mode of operation in the zone i e the weekly schedule However it is possible to turn off the schedule and set a separate t...

Страница 13: ...ing the MENU button Use the MENU button to go to the settings of the time intervals and the set temperature that will be valid for the specified time interval set it using the arrows confirm with the...

Страница 14: ...steresis is 1 C The room sensor will start to indicate room underheating after the temperature drops to 22 C Calibration Room sensor calibration is carried out during assembly or after a longer period...

Страница 15: ...s information to automatically activate the heating in advance of the time required to reach the set temperatures This system does not require any involvement on the part of the user and precisely res...

Страница 16: ...n the zone temperature reaches the set point Once the set point is reached the temperature in the zone will start to drop When it reaches 21 C set temperature minus hysteresis value the actuator will...

Страница 17: ...tration an additional Information function appears where the user can view the sensor parameters e g battery status range etc It is also possible to delete a given sensor or all at the same time 4 1 8...

Страница 18: ...llation from overheating 4 2 ADDITIONAL CONTACTS The function allows you to handle additional contacts First of all it is necessary to register such a contact 1 6 pcs To do this select the Registratio...

Страница 19: ...e Calibration This function can be used to calibrate the built in valve e g after prolonged use During calibration the valve is set to a safe position i e for the CH valve and the Return protection ty...

Страница 20: ...y in a short circuit while the full opening of the valve 100 means that the short circuit is closed and the water flows through the entire central heating system CAUTION If the Boiler Protection is of...

Страница 21: ...When this function is checked the controller will operate according to the Room regulator temperature lower parameter Room regulator temp lower In this setting set the value by which the valve will l...

Страница 22: ...take into account the Self of the valve module or the Main sensor Only in slave mode Boiler protection This provides protection against excessive CH temperature and is intended to prevent dangerous i...

Страница 23: ...e deviations set are in the range of 10 C To enable weekly control select and check Mode 1 or Mode 2 Detailed settings of these modes can be found in the following sections of the submenu Set Mode 1 a...

Страница 24: ...on The user can control the operation of various devices and change some parameters using the emodul pl application The device has a built in Internet module After switching on the Internet module and...

Страница 25: ...to 10 C with a step of 0 1 C In the case of a wireless sensor the subsequent parameters relate to the range and level of the battery 4 7 HEATING STOPPING Function to prevent actuators from turning on...

Страница 26: ...operating mode Heating all zones are heated Cooling all zones are cooled Automatic the controller switches the mode between heating and cooling based on the two state input 4 11 ANTI STOP SETTINGS Thi...

Страница 27: ...sensor Replace the sensor with a new one or contact the service staff if necessary No communication with sensor wireless regulator No range No battery Flat battery Put the sensor regulator in a differ...

Страница 28: ...the controller has been installed properly Replace the batteries Calibrate actuator again by holding the communication button until the third flash of green light Call the service staff ERROR 3 Calib...

Страница 29: ...arried out by a qualified installer After changing the software it is not possible to restore the previous settings Do not turn off the controller while updating the software IX TECHNICAL DATA AC1 loa...

Страница 30: ...equipment implementing provisions of Directive EU 2017 2102 of the European Parliament and of the Council of 15 November 2017 amending Directive 2011 65 EU on the restriction of the use of certain ha...

Страница 31: ......

Страница 32: ......

Отзывы: