HGP Kit Manual
6.0 Troubleshooting
57
Communication Problems
•
J5 Communication Header
o
With the power de-energized from the filter, check wiring leading to J5 header
If the user is using a different RS485 converter than the example above
please follow the datasheet for the A & B signals and ground for proper
setup
•
Ensure the drivers of the RS485 to USB converter is installed to the computer. Simple
way of checking while the RS485 converter connected is to go to the device manager
and scroll down to ports. There will be a device connected to the ports. If your device is
not listed, the user will need to install the correct drivers of the RS485 converter.
•
PQvision App Load Defaults
o
With the RS485 Converter connected to the circuit board
o
Energize Filter
o
Open PQvision desktop interface
o
Go to
Settings
o
Select Load Defaults
o
Select Apply