HGP Kit Manual
4.0 Installation
7
Make sure that the HGP kit is correct for the application. The voltage ratings of the filter kit must
match the input voltage rating of the connected drive. The horsepower and current ratings of the
filter kit must be appropriate for the connected load.
Technical Specifications
Table 1 - HarmonicGuard
®
Passive Filter Technical Specifications
Electrical Characteristics
Voltage Rating
208, 240, 380-415, 440, 480 or 600 VAC
Phase
3
Compliance
IEEE-519 2014
Operating Frequency
50 or 60 Hz
Motor drive input power rating range
1.5 – 1250 HP for 480V units. Power range varies
depending on system voltage.
Immunity from Voltage Distortion
Less than 5% THID at full load with THVD as high as
5%*
Overload Capability
200% of current rating for 3 minutes
Environmental Conditions
Operating Temperature
Kit component ambient: 50°C (122°F)
Storage Temperature
60°C (140°F)
Elevation
Up to 2,000 m without derating
Humidity
95% non-condensing
Agency approvals or certifications
Capacitor Assemblies
UL and cUL Listed
Capacitors
UR and cUR Recognized
Reactors
UR and cUR Recognized
Reactors
UL and cUL Listed
Performance Guarantee
To meet the requirements for the Performance Guarantee the minimum system conditions must
conform to the following:
•
No more than 1.5% Source inductance
•
The input VFD current waveform shall be consistent with that of a VFD with 3% AC line
reactance at full load
Please consult TCI regarding optimum filter performance when applied to DC drives.
4.0
Installation
Installation Guidelines
Installation Checklist
The following are the key points to be followed for a successful installation.
Make sure that the installation location will not be exposed to direct sunlight, corrosive
or combustible airborne contaminants, excessive dirt or liquids.
Select a mounting area that will allow adequate cooling air and maintenance access.