Table 5 – 480 V, 60Hz, HGP
HGP Rating (HP) Watts Loss Tuned Circuit Current (A) Line Current (A)
1.5
80
0.9
3
3
85
1.5
4.8
5
85
2.2
7.6
7.5
115
5.1
11
10
135
5.1
14
15
190
8.6
21
20
230
10.3
27
25
285
13.7
34
30
240
17.1
40
40
435
25.7
52
50
455
25.7
65
60
600
34.2
77
75
750
42.8
96
100
700
51.3
124
125
815
68.4
156
150
1075
77.0
180
200
1325
103
240
250
1475
128
302
300
1875
154
361
350
1725
180
414
400
1775
205
477
450
2000
231
515
500
2300
257
590
600
1975
308
720
700
1975
359
840
800
2025
410
960
900
2250
230/230 (Parallel Branches)
1080
1000
2500
257/257 (Parallel Branches)
1200