HGP Kit Manual
5.0 PQconnect
50
Read Parameters:
Table 30: Network Interface OUTPUT/Feedback Register Map
Parameter Name
I/O Reg
Address
Offset
Signal
Direction
from
Filter
Data Values and Examples
Description
MB_PARITY_RO
302
Output
0 = None
1 = Odd
DEFAULT:
2 = Even
Modbus Parity
RELAY_INPUT_STATUS
320
Output
0 = Enabled
DEFAULT:
1 = Disabled
Digital relay status
RELAY_INPUT_1_CONFIG_RO
321
Output
DEFAULT:
0 = Disabled
1 = Tuning Reactor Thermal
Switch Input
2 = Line Reactor Thermal
Switch Input
3 = Reset Command
4 = External Control Input
Customer external control inputs
RELAY_INPUT_2_CONFIG_RO
322
Output
DEFAULT:
0 = Disabled
1 = Tuning Reactor Thermal
Switch Input
2 = Line Reactor Thermal
Switch Input
3 = Reset Command
4 = External Control Input
Customer external control inputs
SYS_SERIAL_NUM_2_RO
350
Output
Parameter contains UUUU in
the UUUULLLL-NN serial
number format.
Unit serial number section - upper 16 bits
of 32-bit unit job number
SYS_SERIAL_NUM_1_RO
351
Output
Parameter contains LLLL in the
UUUULLLL-NN serial number
format.
Unit serial number section - lower 16 bits
of 32-bit unit job number
SYS_SERIAL_NUM_0_RO
352
Output
Parameter contains NN in the
UUUULLLL- NN serial number
format.
Unit serial number section - two-digit unit
number
SYS_NULL_STAT
400
Output
0 = Not calibrated
1 = Unit is calibrated
System auto null status *
SYS_NULL_TMR
401
Output
0 = Unit is not calibrating
1 = Unit is Calibrating
System null timer; indicates whether the
unit is calibrating*
SYS_INT_HB
402
Output
Range: 0 to 65535
Processor internal heartbeat. Internal
counter that counts up and rolls over to
zero used to verify processor clock
operation. *
SYS_BG_HB
403
Output
Range: 0 to 65535
Processor background heartbeat. Internal
counter that counts up and rolls over to
zero used to verify processor clock
operation *
Содержание HGP HarmonicGuard Series