HGP Kit Manual
6.0 Troubleshooting
58
o
Default Modbus settings should be applied. Try connecting to the COM port
If this doesn’t work de-energize power to the filter and try flipping the A
and B signal wires leading to the J5 header of the circuit board.
•
Hard Reset Modbus settings (Worst Case)
o
To perform a hard reset of Modbus settings the user will need to remove jumper
J20 with the power de-energized from the filter. Once the jumper is removed
connect the RS485 converter to J5 header and energize filter.
o
Open PQvision
o
Confirm there is a COM port under Communication and try to connect
Note if connecting to the COM port does not work, try flipping the A and
B signal wires leading to the J5 header of the circuit board
o
Load defaults and apply
o
Save settings and de-energize filter
o
Connect jumper to J20
o
Energize filter
o
Try connecting to PCB
All modbus settings should be set to default settings at this point
If the board doesn’t connect after trying hard reset contact TCI Tech-
Support
Debug Status Conditions
Based on the status condition there are various ways a status can appear. Some status
conditions are not critical are used as warnings. Before investigating the filter internally,
disengage supply voltage to the filter. If problems persist after initial checks, please contact TCI
Tech-Support.