LEG04
MAN.
TERM.DISIN-
FECTION
Manual
thermal disin-
fection
on/off
-
25
05:084
LEG05
THM.DISINF.
TIMEPRO-
GRAM
Time program
for thermal
disinfection
Time program for enabling the
legionella protection function
-
-
25
05:062
NAC
RECHARGING
Adjuster is visible if
RECHARGING PRIMARY NAC00
(08:100) is set to on.
NAC00 RECHARGING
PRIMARY
Option: Thermal recharging request (see above for
basic parameters)
on/off
off
NAC03 SWITCH ON
RECHARCHIN
G
Switch-on
hysteresis for
the tank set-
point tem-
perature
If the temperature in the tank is
>
setpoint plus setting, a charging
request is ended.
1...30
K
08:063
NAC04 TO SENSOR
TYPE
TO tank top
sensor selec-
tion, sensor
type
n
0: NTC 5K
n
1: PT 1000
n
2: 0…5 V
0 ...2
-
25
28:066
NAC09 RECHARGE
TIME PRO-
GRAM
Time program
for domestic
water
Time program for activating
domestic hot water preparation at
the normal setpoint or for acti-
vating recharging.
-
-
25
05:061
WHF
WARM
HOLDING
FUNCTION
Adjuster is visible if
WARM HOLDING FUNCTION WHF00
(05:113) is set to on.
WHF00 WARM
HOLDING
FUNCTION
Option:
Standby/
warm holding
function
(see above for basic parameters)
on/off
off
25
05:113
WHF01 MIN SWITCH
OFF TIME
Min. switch
off time
The warm holding function is
blocked for the set time if the min-
imum switch-on time has elapsed or
if the flow temperature is reached.
0…60
min. 25
36:040
WHF02 MAX
SWITCH ON
TIME
Min. switch
on time
The warm holding function is
switched off once the set time has
elapsed of if the flow temperature is
reached.
0…30
min. 25
36:041
KOM
COMMUNI-
CATION
KOM01 LANGUAGE
SELECTION
0...8
-
0
04:056
ES 5941
Info and menu parameters
08/2020 Item no. 215790 EA no. 1321
Operating instructions
32