8
Technical data
DESIGNATION/TYPE
ES 5941S
Power supply
230 V AC ± 10 % 50 – 60 HZ
Power consumption, standby
< 1 VA
Max. power consumption
5 VA
Fuse
3.15 AT
Electromechanical relays
5
Switching capacity
6 (2) A
Information, HE pumps
15 A - 4 s or 20 A - 0.4 s at 10%
switching duration
Signal output PWM or 0 - 10 V
2
Inputs, sensors
7 - NTC 5 kOHm or PT 1000
switchable
Inputs, analogue (0...5 V)
2 (4)
Inputs, pulse
1 (2)
Assembly
Wall assembly
Dimensions W/H/D in mm
153.5 x 135.3 x 48.7
Display
LCD segment display
Backlight
Yes
Operation
4 pushbuttons
Ambient / (storage) temperature
0…50 °C (- 20...60 °C), max. 85%;
non-condensing
Loading capacity
max. 180 mA
eBus supply
50 mA
Bus line – length, cross section
2-wire bus, twisted, max. 50 m,
min 0.5 mm²
Designation/type
Outputs (high voltage)
Outputs (low voltage)
Inputs (low voltage)
Housing
eBUS
ES 5941
Technical data
08/2020 Item no. 215790 EA no. 1321
Operating instructions
52