ZIR06
CIRC. CALI-
BRATION
Circulation
flow rate cali-
bration
n
0:
Off
= no calibration.
n
1:
Manual
= calibrate 1x.
No automatic reset to 0. Set to
0 and then to 1 in order to cali-
brate again.
n
2:
Auto
= Calibrate each
Monday at 2 am.
0...2
-
25
36:010
ZIR07
FLOW RATE
CIRCULATION
Circulation
flow rate.
Flow rate when the circulation
pump is active, as a manual entry
or as a metrologically determined
value from ZIR06 CIRCULATION CAL-
IBRATION.
0...999.9
l/min 25
23:111
ZIR10
RUNTIME
CIRC.PUL-
SECON.
Minimum run-
time WWC
If operation of the circulation is
pulse-controlled, the runtime of
the pump WWC is defined with
this value. This minimum runtime
is also applicable in relation to tap
support.
0...30
min
25
05:070
ZIR11
OFFTIME
CIRC.PUL-
SECON.
Off time WWC
Once the runtime ZIR11 OFFTIME
CIRC.PULSECON. (05:070) of pump
WWC has elapsed, operation of
the WWC is blocked for this period
of time. This minimum downtime is
also applicable in relation to tap
support.
0...240
min
25
05:071
ZIR12
CIRC. TIME
PROGRAM
Time program
for domestic
hot water cir-
culation
Time program for enabling the cir-
culation function
-
-
0
05:064
ZIR13
CIRC. MODE
WHEN TAPPED
Circulation
mode during
tapping
Circulation mode is defined during
tapping. This determines whether
the selected circulation mode is
active during tapping or not. Note:
Tap support is always active irre-
spective of this definition.
n
0: on - circulation mode active
during tapping
n
1: off - circulation mode off
during tapping
0...1
-
25
36:032
ZIR14
SWITCH ON
CIRCULATION
Switch-on
hysteresis for
the circula-
tion setpoint
temperature
If the circulation return tempera-
ture does not reach the circula-
tion setpoint temperature minus
the setting, the circulation pump
is switched on.
1...30
K
0
36:035
ES 5941
Info and menu parameters
08/2020 Item no. 215790 EA no. 1321
Operating instructions